PROBLEM AND SOLUTIONS

PROBLEM

PROBABLE CAUSES

SOLUTION SUGGESTIONS

COAL IS NOT BURNING WELL

1) Maybe you

are using the type of

coal other than the ones
recommended.

2) Draft of the

chimney is bad.

3) It is possible that the stove is
getting

air inside from the joining

parts or from the

place where

stove's

pipe enters the wall.

1)

Please

use quality type of coal

having 6000-7000 Kcal/hour and by
having walnut-orange

size.

If you have to use the type of coal

having

less calorie, then please

request

fan group from your dealer.

2)

Please control the draft of the

chimney.

Get it cleaned if required.

Please refer to 'Chimneys Page'

for Further details about the chimneys.
3)

Insulate the joining parts of the

chimney with aluminium bandage.

Please

take up the place where

chimney pipe enters

the wall.

CENTRAL HEATING STOVE IS
BURNING BUT ROOMS ARE
NOT GETTING WARM

1)

Actually, Central Heating Stove is

not burning well. Quality of the coal
is low or Stove is burned

with little

amount

of coal.

2) Maybe you used un-insulated Pipe
while passing from the inside of the
concrete.
3)

Insulation of the site is weak.

4) Central

Heating Stove is just

burned and consequently,

it takes

time for Central

Heating Stove to

reach

a good heat because the walls

are

cold.

1)

Please

use quality type of coal

having 6000-7000

Kcal/hour

and by

having walnut-orange size. Air flow
becomes less when smaller size coal

is used. Do not use damp and too

much ash producing coal.
2) Consult your installer.
3)

Wall and roof insulation must be

done.
4)

This problem disappears after

burning for a certain period of time
and after the walls get

warm

LAST CORE IS NOT GETTING
WARM

1) Horizontal pipe coming to the last
core has

been

used

as small (R 1/2").

2) Spout has occurred towards the
inside at the

source of plastic pipe

and cross-section

of the pipe has

been narrowed.

1) Increase the revolution of the
pump.

If not solved, please consult

your installer.

CHIMNEY'S DRAFT
IS

WELL AND CENTRAL

HEATING

STOVE'S COMBUSTION

DOES NOT SLOW DOWN.

Air

lid

controlled by chain driven

thermostatic

regulator remains open

also

in high temperatures.

Please

make the adjustment for the

length of the chain.

BOILER'S THERMOMETER
RAPIDLY RAISES TO 120°C
HOWEVER CORES DO

NOT GET

WARM

1) Central Heating Stove has
generated air because water has got
less.
2) There

has been vaporizing and

water

loss because

of electricity cut¬

off.
3) Circulation pump has generated air.
4) Circulation pump has malfunctioned.

1) Complete this deficiency. Control
the air of

cores and circulation pump.

2) If you encounter too much of airing
because of having very frequent
electricity cut-offs, then you can use
"Power Supply Having Full Sinus".
3) Please refer to: 3-5.
4)

Please contact the manufacturer

of the Pump.

THERE IS TOO MUCH
VAPORISING

AND CORES DO

NOT GET

WARM

Circulation pump might

have been

connected to boiler's return

by a

mistake. If expansion tank is also at
the same

flat, height difference may

not

be enough and this may

cause

short-circuit

of the hot water over

expansion

tank. They may not get

warm

if air occurs in the radiators.

Connect

the circulation pump as

indicated

in Installation Connection

Diagram (Figure

-

2)

Содержание 301

Страница 1: ...OPERATING MANUAL Please do not use your Central Heating Stove before reading this manual with Fireplace Stoveand Solic Fuel cc MODEL NO English ...

Страница 2: ...We thank you for choosing Yakar Products You will always obtain maximum output When you read this Operating Manual prepared to assist you and as long as you comply with the instructions in it ...

Страница 3: ... THE LOCATION TO PLACE AND INSTALLATION INSTRUCTIONS 4 5 ELECTRICAL DIAGRAM 6 301 and 302 INSTALLATION CONNECTION DIAGRAM 7 OPERATING CENTRAL HEATING STOVE 8 WARNING and RECOMMENDATIONS 9 CHIMNEYS and POINTS TO TAKE INTO CONSIDERATION 10 PROBLEMS and SOLUTION PROPOSALS 11 12 POINTS TO TAKE INTO CONSIDERATION FOR THE GUARANTEE 13 ...

Страница 4: ...rrounding RE FUELLING INTERVALS Burning Condition Fuel Type Re Fuelling Interval Nominal 6 000 kcal hour coal 5 hours Slow 6 000 kcal hour coal 12 hours EXHAUST GAS TEMPERATURE Exhaust Gas temperature is 200 C average Technical Specifications Product Code Capacity Fuel Type Smoke Pipe Diameter Boiler Inlet Outlet Pipe Fuel Capacity Electricity Pump Power Net Weight Width Depth Height 301 16 25 kW ...

Страница 5: ... Rear Housing Lid 15 Riaht Housina Lid 14 Lef Housing Lid 13 Ashtray 12 Oven Glass 11 Cleaning the cover from the too 10 Lid Hamdle 9 Bottom Lid 8 Ceramic Glass 7 Middle Lid 6 Oven Lid 5 Pull And Dump Handle 4 Turninq Handle 3 Pull And Dump 2 Rotary 1 Bowl Grid Figure 1 ...

Страница 6: ... with conic pipe couplings 2 12 Steam exit taking place on the expansion tank must be extended to restroom bathroom or to ventilation medium 2 13 Main line pipes of the installation must be R1 one finger Horizontal pipes for the final cores are selected as R 3 4 2 14 Very good heat insulation must be done for the pipes passing from the concrete floor Otherwise adequate heat can not be obtained fro...

Страница 7: ...r Outlet 9 Water Flow Back To Boiler 10 Indicator Light 11 Thermometer thermostat 12 Water Level Indicator 13 herald steam dispose 14 steam outlet Make the installation of radiator heaters to structure with Conical Record so that the installation and dismantling would be easier During the installation we connect the water to boiler at 09 from the water line Expansion Boiler Figure 2 Installation c...

Страница 8: ... be turned once with the screwdriver Big yellow screw is applied to its place when shaft starts to turn 3 6 Air of the cores must be removed Water level of expansion tank must be controlled 3 7 Water is given to the system from boiler s inlet pipe Figure 2 9 from service water line 3 8 After becoming sure that there is no leakage in the system fuel is loaded to the firing chamber and then the fire...

Страница 9: ...te COKE Mix with Lignite with 1 3 rate WOOD Hu Hu Hu Hu Hu Hu Hu Hu 6650 7900 6500 7000 3200 4500 2500 3200 1100 2500 7000 7300 4500 5500 2000 3500 Kcal h Kcal h Kcal h Kcal h Kcal h Kcal h Kcal h Kcal h a Good Draft b Average Draft c Bad DraftCeki CHIMNEYS and POINTS TO TAKE INTO CONSIDERATION Pipes of Central Heating Stove must be as short and they must be in vertical direction as much as possib...

Страница 10: ...mmended one bracket FALSE RIGHT Figure 7 Expansion Connection Yanh Yanh Dogru Yanh Yanh Figure 6 Chimney Connection Expansion must be connected to boiler at least 1 degree incline s Figure 7 The roof ridge must be at least 80cm also smoke outlet should be through the window as well as If there is ash drawer it should be canceled Figure 8 Figure 8 Pipe and chimney connection ...

Страница 11: ...ll and roof insulation must be done 4 This problem disappears after burning for a certain period of time and after the walls get warm LAST CORE IS NOT GETTING WARM 1 Horizontal pipe coming to the last core has been used as small R 1 2 2 Spout has occurred towards the inside at the source of plastic pipe and cross section of the pipe has been narrowed 1 Increase the revolution of the pump If not so...

Страница 12: ...o either one of the seller dealer representative importer or manufacturer producer of the product when there is no service station If the malfunction of the product can not be eliminated within 30 Thirty days then the manufacturer producer or importer has the compulsion to allocate another product to the consumer by having similar characteristics until the repair of the products gets completed 4 I...

Страница 13: ......

Страница 14: ... the boiler water reach 70 90 C hot utility water can be obtained for a long period of time 6 HOW IS YOUR FURL COMBUSTION QUALITY In a good combustion after ignition and inflammation stage flame becomes red or orange color Glowing coal becomes eye popping brilliant In a weak combustion top surface of the coal is black during combustion and when the combustion ends some part of the coal remains unb...

Отзывы: