H-3553T Combo Bubbler Setup Menu SDI-12 Interface
B – Bubbler Settings
Command: aXWPSnn!
:
Response: a0061
Bubbler Settings Menu
Command: aXRPS!
S – Purge Sustain: xx
Response: a0021
Enter Purge Sustain (10 - 40) [ nn ]
Command: aD0!
Response: a + nn
Table 4-16: Change the H-3553T Purge Sustain
SETUP & OPERATION
22
4-20 Milliamp Output
The H-3553T has the ability to output the
stage value as a 4-20 milliamp signal. The
4-20 milliamp output is most commonly
used in industrial applications with PLC’s
or SCADA systems. The H-3553T controls
the loop current but does not power the
loop. Therefore, the loop must be externally
powered. Figure 4-1 shows a basic wiring
diagram for a 4-20 milliamp output loop with
the H-3553T. The battery in the loop should
be a +24VDC power source.
Figure 4-1: Typical H-3553T 4-20 mA Output Setup
The H-3553T scales the current measured stage reading for the 4-20 milliamp output based on the 4-20
milliamp min and max stage values.
4-20 Milliamp Min Stage
The 4-20 milliamp min stage value should be the lowest the stage gets at the installed site. When the stage
equals this value or lower the 4-20 milliamp out put will be 4.0 milliamps, the min.
The H-3553T 4-20 milliamp min stage default value is set to 4. There is no limit to this value, but keep in mind
that the smaller the overall range of the 4-20 stage scalar, which is the min to the max stage, the more accurate
the 4-20 milliamp output will be. To change the 4-20 milliamp min stage using the RS-232 main menu, press
the ‘P’ key to enter the “Advanced Options” menu and then press the ‘F’ key to enter the “4-20mA Output
Setup” menu. Then press the ‘N’ key in this menu and enter in the new “Min Stage” value and press the ‘Enter’
key.
To change the H-3553T 4-20 milliamp min stage using the SDI-12 interface, send the “aXWILn.nn!” SDI-12
extended command. The response should be “a0021”, which means that it could take 2 seconds to complete
the command and then it will put 1 data value in the buffer. To check the new 4-20 milliamp min stage, send
“aXRIL!” command and wait the responded time. Then send the “aD0!” command to read back the new written
4-20 milliamp min stage. Note Table 4-17, the ‘a’ is the current SDI-12 address of the H-3553T and the ‘x.xx’
is
the current 4-20 milliamp min stage and the ‘n.nn’ is the desired 4-20 milliamp min stage.