Message
No.
Message shown on the display
Description /
Possible Cause
Countermeasures
73
PSU:DI21.0 Alarm cabinet temperature high
Temperature in cabinet too high.
Cable break.
Ambient temperature too high.
Check cabinet temperature.
Check temperature probe.
Check function of chiller.
Refer to
manufacturer’s manual.
74
PSU:DI21.1 Alarm fault air condition 1
Fault message from air condition.
Cable break.
Incorrect wiring.
Eco mode activated on Rittal air-
condition.
Check cables and connections.
Check the fault message on the
display, take countermeasures
according to the operating
instructions of the unit,
refer to
manufacturer’s manual.
75
PSU:DI21.2 Alarm fault air condition 2
Fault message from air condition,
Cable break,
Incorrect wiring.
Eco mode activated on Rittal air-
condition.
Check the fault message on the
display, take countermeasures
according to the operating
instructions of the unit,
refer to
manufacturer’s manual.
76
PSU:DI21.3 Alarm fault air condition 3
Fault message from air condition,
Cable break.
Incorrect wiring
Eco mode activated on Rittal air-
condition.
Check the fault message on the
display, take countermeasures
according to the operating
instructions of the unit,
refer to
manufacturer’s manual.
77
PSU:DI21.4 Alarm cabinet door open
Cabinet door open.
Cable break.
Close door.
Check door switch.
Check cables and connections.