background image

WQG-10029-01

Note: If meter output data is available in pulses per cubic foot, this 

step can be eliminated.

Multiply the pulses per cubic feet by the quantity 
to be indicated.

Since the circuitry is only capable of handling 
whole numbers, the factor must be rounded to 
the nearest whole number (1773).

Note: When the factor must be rounded off, a small error is 

introduced—in this example, .0028%. New meters being shipped 

from the factory are geared to eliminate this error or maintain it at a 

minimum, if possible. In applications where no error is tolerable, the 

ACT-PAK instrument line contains provisions for an error correction 

circuit and/or an input pulse scaler.

To start, place all of the 12 switches in the OFF 
position. Setting the factor into the instrument is 
accomplished by turning the dip switch ON so 
that the sum of the factors equals the number 
desired. There is a unique combination of factors 
for each desired number. They are determined 
in the following manner: select the largest binary 
number from the chart that does not exceed the 
balance, continue selecting and subtracting until 
the balance equals zero. At this point, all factors 
subtracted must be set into the instrument by 
placing the associated switch in the ON position.

Act-Pak® Electronic Instrumentation

Models 1100D and 1100DN Quick Guide

Adjusting Option M Multiplier

The multiplier circuit is configured in binary coded 
decimal (BCD) and is  adjustable to any number 
between 0.0001 and .9999. To set the multiplier, the 
following procedure is suggested:

1.  Determine the multiplier necessary to indicate the 

units required.

2.  Remove the Act-Pak front panel assembly from 

the instrument cabinet and locate the multiplier 
module. 

Note: Multiplier is a separate PC board in the center of the instrument 

assembly.

3.  Rotate the assembly so the printing on the 

multiplier circuit board is readable from left to right, 
as shown in the next illustration.

4.  Setting the multiplier is accomplished by rotating 

the pointer on the digits associated switch to the 
number desired using a small screwdriver. 

 

t

CAUTION

The switch selector must be in the detent and not left 

between two digits or erratic operation will result.

Содержание SENSUS Act-Pak 1100D

Страница 1: ...o the metering device and instrument before applying power 2 If it becomes necessary to disconnect any of these connections first remove the AC power to the instrument Meter or Signal Output Terminal Number Function Wire Color Switch Inputs Belden 8760 Wire Color Solid State Inputs Belden 8770 13 12VDC No Connection Red 16 Input Signal White White 14 Ground Black Black 15 Shield Bare Shield Bare S...

Страница 2: ...17 VAC All resistive loads Option C1 SS 50 mA at 24 VDC Typical Series 1100 Act Pak Wiring Connection Diagrams AC Power Inputs Terminal Number Function 3 Earth Ground 2 117 VAC 1 117 VAC Proportional Output Terminal Number Function 5 Positive 6 Negative Option B Terminal Number Function 10 Normally Closed Contact 11 Common 12 Normally Open Contact Option C1 C1 SS Terminal Number Function Relay Fun...

Страница 3: ...ext digit To start the least significant digit flashing momentarily depress the RST button To exit the programming mode and save all parameters step through the module until one of the four main modules is displayed then press the RST button until Pro nO displays Pressing the SEL button at this point enters the data and closes the program mode Program Menus Module 1 1 inPUt InP A b dual cnt CntA d...

Страница 4: ... a contact closure based on the flow rate set to rATE For pulsed outputs based on total set to Count A SPt ACT If rate was selected above to bound if contacts are to close when the setpoint is exceeded Act Pak Electronic Instrumentation Models 1100D and 1100DN Quick Guide and open below the setpoint To latch or hold the contacts closed once the flow rate is exceeded set to LAtCH A manual reset is ...

Страница 5: ...t binary number from the chart that does not exceed the balance continue selecting and subtracting until the balance equals zero At this point all factors subtracted must be set into the instrument by placing the associated switch in the ON position Act Pak Electronic Instrumentation Models 1100D and 1100DN Quick Guide Adjusting Option M Multiplier The multiplier circuit is configured in binary co...

Страница 6: ...caution when working with disassembled AC electrical components Act Pak Electronic Instrumentation Models 1100D and 1100DN Quick Guide Calibration Proportional Output 4 20 mA with a Voltmeter 1 Connect a load resistor across terminals 5 and 6 2 This resistor may be of any value less than or equal to 500 ohms 3 Connect a digital voltmeter across terminals 5 and 6 4 Apply power to the instrument wit...

Страница 7: ... circuit board 3 Note that the AC line cord is attached to terminals 1 2 and 3 4 Use the tables in the manual to connect the meter and control devices 5 To attach wires loosen the appropriate screw on the connector 6 Run the wires through the enclosure and place in the opening on the connector at the proper location and tighten the screw 7 Do not leave bare wires extending outside the connector 8 ...

Отзывы: