background image

24V Burner/120V Feeder

120V Burner/120V Feeder 

or

24V Burner/24V Feeder

Connect a wire from the "Hot" side of the power supply to the
water feeder terminal 3, and low water cut-off terminal 2.
Connect a wire from the neutral side of the power supply to the
water feeder terminal 2, and to the neutral side of the burner.

Connect the wire from the burner to terminal 1 of the low water
cut-off. Connect a jumper from terminal 2 to terminal 3 of the
low water cut-off. Connect a wire from terminal 4 of the low
water cut-off to terminal 1 of the water feeder.

W
or

1

N

or

2

H

or

3

BURNER

1

2

3

4

N

H

WF2-U-120 or
WF2-U-24

Supply Voltage

SAME as Feeder

69

120V Burner/24V Feeder

W
or

1

N

or

2

H

or

3

BURNER

24V
TRANSFORMER

1

2

3

4

N

120 VAC

SUPPLY

H

WF2-U-24V

69

Switch

Initial

Initial

Dwell/Feed

Position

Dwell

Feed

Cycles

M&M

60

60

Repeats until LWCO

seconds

seconds

reactivates the 

burner circuit

2

90

90

One

seconds

seconds

3

100

100

One

seconds

seconds

2

3

M

&M

M&M

2

3

Wiring Diagrams (continued):
Series 69 Low Water Cut-off with M&M Model WF-2-U Electronic Water Feeders

The Uni-Match

®

water feeders have a three-position slide

switch which initiates a dwell period specific to the position of
the switch. If the system condensate raises the boiler water
level above the cut-off level during the dwell period, no addi-
tional water will be added to the boiler. Once the dwell period
has passed, the feeder will be activated and water will be
added to the boiler. The feeder will be deactivated when the
LWCO reactivates the burner circuit.

The position of the slide switch also sets the length of the
dwell period, the length of time valve is open and the number
of dwell/feed cycles. The control is set with the slide switch in

position 3

and can be changed in the field after installation.

The chart on the right indicates the cycles and length of
dwell/feed cycles for each position.

6

W
or

1

N

or

2

H

or

3

BURNER

24V

TRANSFORMER

1

2

3

4

N

120 VAC
SUPPLY

H

WF2-U-120

69

WIRING ALTERNATIVES

WHEN USING MIXED VOLTAGES

Содержание McDonnell & Miller 69 Series

Страница 1: ...series with the burner control circuit to provide safety redundancy protection should the boiler experience a low water condition Moreover at each annual outage the low water cut offs should be disma...

Страница 2: ...D AS PILOT SWITCH IN SERIES WITH HOLDING COIL OF AUTOMATIC STARTER NEUTRAL WIRE TO TWO WIRES OF 101A OR TO ALARM CIRCUIT HOT WIRE TO BURNER JUMPER SAFETY SWITCH 02 04 10 30 USED WITH MODEL 101 ELECTRI...

Страница 3: ...ete the installation by securing the control onto the barrel by tightening the eight 8 clamping ring screws to 5 ft lbs 7 N m torque TOP on the switch terminal panel MUST be in the up position INSTALL...

Страница 4: ...th M M Model 101 A Electronic Water Feeders 120V Burner and 120V Feeder BURNER 120 VAC SUPPLY 1 2 3 4 N H 101A 69 Using a wire nut connect a wire from the neutral side of the power sup ply to one of t...

Страница 5: ...ater Feeder Millivolt Burner Control and Model 101 A 120V Water Feeder 24V TRANSFORMER 101 24V 48 1 2 3 4 101A 24 A C D B E 120 VAC SUPPLY WIRE NUTS MILLIVOLT BURNER CIRCUIT Wire only terminals 1 and...

Страница 6: ...seconds seconds 3 100 100 One seconds seconds 2 3 M M M M 2 3 Wiring Diagrams continued Series 69 Low Water Cut off with M M Model WF 2 U Electronic Water Feeders The Uni Match water feeders have a t...

Страница 7: ...9...

Страница 8: ...poses Seller warrants the goods purchased hereunder with the exception of membranes seals gaskets elastomer materials coatings and other wear parts or consumables all of which are not warranted except...

Отзывы: