Turn the boiler off.

Drain the water in the boiler to a level which is below the 
tapping on the boiler. Allow the boiler to cool to 80˚F (27˚C) 
and allow the pressure to release to 0 psi (0 bar).

Determine where to install the control. The low water cut-off 
must be positioned at or above the boiler manufacturer’s 
minimum safe water level.

Separate the mounting barrel from the control slightly by 
loosening the eight (8) slotted screws on the clamping ring.
This allows the barrel to be turned into the tapping in the 
boiler without rotating the whole control. (The barrel may 
also be completely removed to install easily).

Apply a small amount of pipe dope or thread sealant to the 
2 1/2 NPT and hand screw the barrel into the boiler without 
rotating the rest of the control. Tighten the barrel securely 
using a pipe wrench to about 150 ft-lbs. (200 N•m) torque.

Rotate the control in the barrel to the finished position using 
a level to set the two (2) conduit housing screws (AA) in a 
horizontal position. Complete the installation by securing the 
control onto the barrel by tightening the eight (8) clamping 
ring screws to 5 ft-lbs (7 N•m) torque. "TOP" on the switch 
terminal panel MUST be in the up position.

INSTALLATION –

TOOLS NEEDED:

One (1) flathead screwdriver, one (1) level indicator
and one (1) pipe wrench.

3

Installation of the Low Water Cut-Off

minimum safe

water level

AA

Clamping ring

and 8 screws

Cut-off

level

The center line on the casting of the Series 69 must be installed above the lowest permissible water level 
determined by the boiler manufacturer.

Whether the gauge glass is mounted directly into the boiler or on an independent water column, the cut-off line on
the 69 control should be mounted 1/2” (15mm) above the lowest visible point of the gauge glass.

IMPORTANT:

Follow the boiler manufacturer's

instructions along with all applicable codes and
ordinances for piping, blow down valve and water
gauge glass requirements.

NOTE: To connect wires to the terminals on
the water feeder, burner, or low water cut-off,
place the bare end of the wire under the termi-
nal screw and tighten the screw with a flathead
screwdriver.

Cover

Using a flathead screwdriver, remove the one (1)
screw that secures the switch cover.

Содержание McDonnell & Miller 69 Series

Страница 1: ...series with the burner control circuit to provide safety redundancy protection should the boiler experience a low water condition Moreover at each annual outage the low water cut offs should be disma...

Страница 2: ...D AS PILOT SWITCH IN SERIES WITH HOLDING COIL OF AUTOMATIC STARTER NEUTRAL WIRE TO TWO WIRES OF 101A OR TO ALARM CIRCUIT HOT WIRE TO BURNER JUMPER SAFETY SWITCH 02 04 10 30 USED WITH MODEL 101 ELECTRI...

Страница 3: ...ete the installation by securing the control onto the barrel by tightening the eight 8 clamping ring screws to 5 ft lbs 7 N m torque TOP on the switch terminal panel MUST be in the up position INSTALL...

Страница 4: ...th M M Model 101 A Electronic Water Feeders 120V Burner and 120V Feeder BURNER 120 VAC SUPPLY 1 2 3 4 N H 101A 69 Using a wire nut connect a wire from the neutral side of the power sup ply to one of t...

Страница 5: ...ater Feeder Millivolt Burner Control and Model 101 A 120V Water Feeder 24V TRANSFORMER 101 24V 48 1 2 3 4 101A 24 A C D B E 120 VAC SUPPLY WIRE NUTS MILLIVOLT BURNER CIRCUIT Wire only terminals 1 and...

Страница 6: ...seconds seconds 3 100 100 One seconds seconds 2 3 M M M M 2 3 Wiring Diagrams continued Series 69 Low Water Cut off with M M Model WF 2 U Electronic Water Feeders The Uni Match water feeders have a t...

Страница 7: ...9...

Страница 8: ...poses Seller warrants the goods purchased hereunder with the exception of membranes seals gaskets elastomer materials coatings and other wear parts or consumables all of which are not warranted except...

Отзывы: