background image

STEP 4 - Installing Series 247/247-2 Water Feeder to Boiler

Burner

Boiler

City Water Supply

Return

Header

Series 247
Water 
Feeder

Casting
Line

ByPass

Valve

Pipe the Series 247/247-2 water feeder so that
the line on the casting is 3" (76mm) above the
minimum safe operating level as specified by
the boiler manufacturer.

Recommended Piping

STEP 5 - Piping the valve on the Models 47/47-2 and 247/247-2

TO BOILER

By-Pass

Valve

Swing Check

STEP 6 - Electrical Wiring (Only for Series 47-2 & 247-2)

AA

a.

Using the flathead screwdriver, loosen the two 
(2) screws that secure the switch cover (AA).

Remove cover.

7

!

IMPORTANT

Boiler manufacturer schematics should always be followed. In the event that the boiler manufacturer's schematic
does not exist, or is not available from the boiler manufacturer, refer to the schematics provided in this document.

a.

Follow the drawing to the right for piping the valve 
to the boiler and city water supply. When piping the 
valve, remember to leave room for servicing the 
valve.

b.

Piping the valve this way will aid in troubleshooting 
the valve and piping in the future.

Содержание McDonnell & Miller 247 Series

Страница 1: ...nt Low Water Cut Off controls be installed on all steam boilers with heat input greater than 400 000 BTU hour or operating above 15 psi steam pressure At least two controls should be connected in seri...

Страница 2: ...2 NPT 47 47 2 Maximum Boiler Pressure 25 psi 1 76 kg cm2 247 247 2 Maximum Boiler Pressure 30 psi 2 1 kg cm2 Electrical Ratings Series 47 Water Feeders and Series 47 2 Combination Water Feeder Low Wat...

Страница 3: ...GS PARALLEL TO BOILER WITH TURNEDY FITTINGS 3 STEP 1 Determine Best Position to Install the Water Feeder to clear obstructions that may be encountered on the side of the boiler INSTALLATION TOOLS NEED...

Страница 4: ...E are greater than 14 356 mm apart invert the black Y casting F as depicted in the diagram to the bottom right and install a longer nipple G F INVERTED Y CASTING Note Reverse union nuts packing and p...

Страница 5: ...onnection Slide union nut U over tailpiece P Using a pipe wrench tighten the tailpiece P into the 1 2 15 mm NPT tapping Q in the lower half of body K Tighten to 54 ft lb 74 N m 5 J H K e Remove the pl...

Страница 6: ...b 74 N m Tighten both union nuts U b Reinstall water glass and gauge connections to Y fittings T When using pipe or tape sealant on the external threads of pipes or fittings follow the manufacturers i...

Страница 7: ...lectrical Wiring Only for Series 47 2 247 2 AA a Using the flathead screwdriver loosen the two 2 screws that secure the switch cover AA Remove cover 7 IMPORTANT Boiler manufacturer schematics should a...

Страница 8: ...in the diagram to the right Low water cut off switch and or low water alarm Pilot switch for motor starter or relay The feeder should be blown down after initial installation before leaving site It s...

Страница 9: ...he flooding Broken Union Test E D B H x 4 A Using a 1 2 socket wrench unscrew the four 4 hex head bolts B that secure the strainer basket H to the valve assembly E B Using a 13 16 socket wrench unscre...

Страница 10: ...er Solution Replace float e Cause Equalizing piping is plugged Solution Clean or replace piping f Cause Water supply is above 150 psi Solution Install pressure reducing valve to reduce water pressure...

Страница 11: ...surfaces DO NOT use sharp objects to scrape off any accumulations of sediment or debris Unit is making noise a Cause Under certain system conditions there may be a vibration when the valve mechanism...

Страница 12: ...er needs Developing new technologies that will improve the way water is used conserved and re used in the future is central to our work We move treat analyze and return water to the environment and we...

Отзывы: