background image

10

TROUBLESHOOTING

The following is intended as a guide to determine why the feeder may not be operating as intended. Please note that
there can be system and installation issues that can affect the operation of the feeder. This includes but is not limited to
the following:

• Piping not installed properly

• Priming and foaming of boiler water

• Faulty check valve in return header

• Delay in condensate returning to boiler

• Tankless coil leaking

Boiler is getting too much water.

a)

Cause:

There is something preventing the valve 

(cartridge poppet) from completely closing.

Test:

Perform broken union test.

Solution:

Remove and inspect cartridge. Clean or 

replace as necessary.

b)

Cause:

By-pass valve is leaking.

Test:

Perform broken union test.

Solution:

Repair or replace valve.

c)

Cause:

Float chamber clogged with sediment.

Test:

Open blow-down valve. If there is little or no 

water flow, the chamber may be clogged with sediment.

Solution:

Remove bottom of float chamber. Clean 

sediment from chamber, float and bellows mechanism.
Replace control if necessary.

d)

Cause:

Float has filled with water.

Solution:

Replace float.

e)

Cause:

Equalizing piping is plugged.

Solution:

Clean or replace piping.

f)

Cause:

Water supply is above 150 psi.

Solution:

Install pressure reducing valve to reduce 

water pressure.

Boiler is not getting enough water.

a)

Cause:

There is something preventing the valve 

(cartridge poppet) from fully opening.

Test:

Perform broken union test.

Solution:

Remove and inspect cartridge. Clean or 

replace as necessary.

b)

Cause:

Strainer clogged with sediment.

Test:

Perform broken union test.

Solution:

Remove and inspect strainer. Clean or 

replace as necessary.

c)

Cause:

Float chamber clogged with sediment.

Test:

Open blow-down valve. If there is little or no 

water flow, the chamber may be clogged with sediment.

Solution:

Remove bottom of float chamber and clean 

sediment from chamber, float and bellows mechanism.
Replace control if necessary.

d)

Cause:

Feed line between valve and boiler is partially 

plugged.

Test:

Perform broken union test. With union broken, 

there should be water flowing through the piping from 
the boiler.

Solution:

Clean or replace piping.

e)

Cause:

Feed line between valve and city water supply 

is plugged.

Solution:

Clean or replace piping.

f)

Cause:

Water supply pressure is less than boiler 

pressure.

Solution:

Reduce boiler pressure or convert to pumped 

return.

Содержание McDonnell & Miller 247 Series

Страница 1: ...nt Low Water Cut Off controls be installed on all steam boilers with heat input greater than 400 000 BTU hour or operating above 15 psi steam pressure At least two controls should be connected in seri...

Страница 2: ...2 NPT 47 47 2 Maximum Boiler Pressure 25 psi 1 76 kg cm2 247 247 2 Maximum Boiler Pressure 30 psi 2 1 kg cm2 Electrical Ratings Series 47 Water Feeders and Series 47 2 Combination Water Feeder Low Wat...

Страница 3: ...GS PARALLEL TO BOILER WITH TURNEDY FITTINGS 3 STEP 1 Determine Best Position to Install the Water Feeder to clear obstructions that may be encountered on the side of the boiler INSTALLATION TOOLS NEED...

Страница 4: ...E are greater than 14 356 mm apart invert the black Y casting F as depicted in the diagram to the bottom right and install a longer nipple G F INVERTED Y CASTING Note Reverse union nuts packing and p...

Страница 5: ...onnection Slide union nut U over tailpiece P Using a pipe wrench tighten the tailpiece P into the 1 2 15 mm NPT tapping Q in the lower half of body K Tighten to 54 ft lb 74 N m 5 J H K e Remove the pl...

Страница 6: ...b 74 N m Tighten both union nuts U b Reinstall water glass and gauge connections to Y fittings T When using pipe or tape sealant on the external threads of pipes or fittings follow the manufacturers i...

Страница 7: ...lectrical Wiring Only for Series 47 2 247 2 AA a Using the flathead screwdriver loosen the two 2 screws that secure the switch cover AA Remove cover 7 IMPORTANT Boiler manufacturer schematics should a...

Страница 8: ...in the diagram to the right Low water cut off switch and or low water alarm Pilot switch for motor starter or relay The feeder should be blown down after initial installation before leaving site It s...

Страница 9: ...he flooding Broken Union Test E D B H x 4 A Using a 1 2 socket wrench unscrew the four 4 hex head bolts B that secure the strainer basket H to the valve assembly E B Using a 13 16 socket wrench unscre...

Страница 10: ...er Solution Replace float e Cause Equalizing piping is plugged Solution Clean or replace piping f Cause Water supply is above 150 psi Solution Install pressure reducing valve to reduce water pressure...

Страница 11: ...surfaces DO NOT use sharp objects to scrape off any accumulations of sediment or debris Unit is making noise a Cause Under certain system conditions there may be a vibration when the valve mechanism...

Страница 12: ...er needs Developing new technologies that will improve the way water is used conserved and re used in the future is central to our work We move treat analyze and return water to the environment and we...

Отзывы: