4.4.3.2 Cables
NOTICE:
The cables that are connected to the control module must meet the following requirements:
• 0.75 mm² (AWG 18)
• Minimum temperature rating: +105⁰C (+221⁰F)
• Conductors must be copper.
4.4.3.3 Connection chart
on page 48.
1
Isolator
1
2
3
4
5
6
A1
A2
Contactor FWD
1
2
3
4
5
6
95
96
97
98
OL
1
2
3
4
5
6
A1
A2
Contactor REV
CT
230VAC/
24VDC
L1 L2 L3 PE
L1 L2 L3
T1 T2
FS+ FS-
Remove for 200~240V Variant
RLY_COM
RLY_FWD RLY_REV RLY_RUN RLY_FAULT
+24V_I N 0V CT1+ CT1-
F/S+ F/S-
CCI-A (T2) CCI-B (T1)
LED 0V RED YEL GRN
V3
V2
V1
A-O/L+
Filter
690:230 V
ACDC
SMPS
Circuit
CB
CB
Breaker
PE
PE
SHIELD
1 2
5 6
PE
2
PE
PE
Fuse
Transformer
PE
3
4
5
WS011305A
1. Control module
2. Status lamp
3. Pump
4. Float switch
5. Power supply
4 Installation
DCM 711 Installation, Operation, and Maintenance Manual
23