Terminal
Description
Terminal
Description
13, 14
Analog input 0/4 -20 mA,
+12 VDC, GND
T3, T4
Temperature stator winding:
Thermal contact or thermistor,
TC
4.6.7 Connect the cables: Pumps with MiniCAS or MAS 711
4.6.7.1 Connect the SUBCAB cable to the pump
NOTICE:
Leakage into the electrical parts can cause damaged equipment or a blown fuse. Keep the
end of the motor cable dry at all times.
For more information about the cable entry, see the Parts List.
1. Remove the entrance cover and the O-ring from the stator housing.
This provides access to the terminal board.
2. Check the data plate to see which connections are required for the power supply.
3. Arrange the connections on the terminal board in accordance with the required power
supply.
Links (jumper strips) are not used with the Y/D start.
4. Connect the mains leads (L1, L2, L3, and ground (earth) ) according to the applicable
cable chart.
The ground (earth) lead must be 120 mm (4.8 in.) longer than the phase leads in the
junction box of the unit.
5. Make sure that the pump is correctly connected to ground (earth).
6. Connect the control leads to the applicable terminal board, and twist the leads together.
7. Make sure that any thermal contacts incorporated in the pump are properly connected to
the terminal board.
8. Install the entrance cover and the O-ring on the stator housing.
9. Fasten the screws on the entrance flange so that the cable insertion assembly bottoms
out.
4.6.7.2 Connect the SUBCAB cable to the starter and MiniCAS monitoring equipment
If there are two power cables, then the cable that is connected to T1 and T2 is labeled. If a
separate control cable is used, then the control leads in the power cable are never
connected.
DANGER: Explosion/Fire Hazard
Special rules apply to installations in explosive or flammable atmospheres. Do not install the
product or any auxiliary equipment in an explosive zone unless it is rated explosion-proof or
intrinsically-safe. If the product is rated explosion-proof or intrinsically-safe, then see the
specific explosion-proof information in the safety chapter before taking any further actions.
NOTICE:
Either thermal contacts or thermistors are incorporated in the pump.
NOTICE:
Thermal contacts must never be exposed to voltages higher than 250 V, breaking current
maximum 5 A.
4 Installation
P7030, P7035, P7040 Installation, Operation, and Maintenance Manual
45