PAGE 17
Aquavar IPC Start-Up Genie
CentriPro
CHAPTER 9: COMMUNICATION
This setup configures the on board fieldbus communications.
• Protocol: Select the protocol for the FC port. (Terminals 61,68,69)
• BACnet
• Modbus RTU
• FLN
• FC MC
• Metasys N2
• FC
• Address: Enter the address for the FC port. The valid range depends on the
protocol.
• Baud Rate: Select the Baud rate for the FC Port.
• Parity/Stop Bits: Parity and stop bits selection for the FC ports.
• Minimum Response Delay: Specify the minimum delay time between receiving
a request and transmitting a response. This is used for overcoming modem
turnaround delays.
• Maximum Response Delay: Specify the maximum permissible delay time
between transmitting a request and receiving a response. Exceeding this delay
time will cause control time-out.
• Maximum Inter-Char Delay: Specify the maximum permissible time interval
between the receipts of two bytes. This parameter activates time-out if
transmission is interrupted. This parameter is not active when Protocol is set to
FC [0] protocol.
• Estimated Cycle Time
• Coasting Select: Select control of the coasting function via the terminals and/or
via the bus.