Aquavar Intelligent Pump Controller

CentriPro

Symptom

Possible cause

Test

Solution

Motor running in wrong direction

Motor rotation limit

Check that 

4–10 Motor Speed

Direction

 is programmed correctly.

Program correct settings

Active reverse signal

Check if a reversing command is

programmed for the terminal in

parameter group 

5–1* Digital

inputs

.

Deactivate reversing signal

Wrong motor phase connection

Motor is not reaching maximum

speed

Frequency limits set wrong

Check output limits in 

4–13 Motor

Speed High Limit [RPM]

4–14

Motor Speed High Limit [Hz]

 and

4–19 Max Output Frequency

.

Program correct limits

Reference input signal not scaled

correctly

Check references input signal

scaling in 

6–0* Analog I/O Mode

and parameter group 

3–1*

References

. Reference limits in

parameter group 

3–0* Reference

Limit

.

Program correct settings

Motor speed unstable

Possible incorrect parameter

settings

Check the settings of all motor

parameters, including all motor

compensation settings. For closed

loop operation, check PID settings.

Check settings in parameter group

1–6* Analog I/O mode

. For closed

loop operation, check settings in

parameter group 

20–0* Feedback

.

Motor runs rough

Possible over-magnetization

Check for incorrect motor settings

in all parameters

Check motor settings in parameter

groups 

1–2* Motor Data

1–3* Adv

Motor Data

, and 

1–5* Load Indep.

Setting

.

Motor will not brake

Possible incorrect settings in the

brake parameters. Possible too

short ramp down times

Check brake parameters. Check

ramp time settings

Check parameter group 

2–0* DC

Brake

 and 

3–0* Reference Limits

.

Open power fuses or circuit

breaker trip

Phase to phase short

Motor or panel has a short phase

to phase. Check motor and panel

phase for shorts

Eliminate any shorts detected

Motor overload

Motor is overloaded for the

application

Perform startup test and verify

motor current is within

specifications. If motor current is

exceeding nameplate full load

current, motor may run only with

reduced load. Review the

specifications for the application.

Loose connections

perform pre-startup check for

loose connections

Tighten loose connections

Input current imbalance greater

than 3% (not applicable for single

phase drives)

Problem with mains power (see

Alarm 4 input phase loss

description in the Warnings and

Alarms table)

Rotate input power leads into the

frequency converter one position A

to B, B to C to A.

If imbalanced leg follows the wire,

it is a power problem. Check

mains power supply.

Problem with the frequency

converter

Rotate input power leads into the

frequency converter one position:

A to B, B to C, C to A

If imbalance leg stays on same

input terminal, it is a problem with

the unit. Contact the supplier.

Motor current imbalance greater

than 3%

Problem with motor or motor

wiring

Rotate output motor leads one

position: U to V, V to W, W to U.

If imbalanced leg follows the wire,

the problem is in the motor or

motor wiring. Check motor and

motor wiring.

Problem with the frequency

converters

Rotate output motor leads one

position: U to V, V to W, W to U.

If imbalance leg stays on same

output terminal, it is a problem

with the unit. Contact the supplier.

9  Troubleshooting

Aquavar

®

 Intelligent Pump Controller INSTRUCTION MANUAL

119

Содержание Aquavar IPC

Страница 1: ...Aquavar IPC WARNINGS AND ALARMS DOCUMENT INSTRUCTION MANUAL IM299...

Страница 2: ...ears for a fault in the input rectifier on the frequency converter Options are programmed at 14 12 Function at Input Imbalance not applicable for single phase drives Check the supply voltage and suppl...

Страница 3: ...tor Current is correct 11 Motor thermistor over temp The thermistor might be disconnected Select whether the frequency converter gives a warning or an alarm in 1 90 Motor Thermal Protection Check for...

Страница 4: ...0 FC Type 15 41 Power Section 15 42 Voltage 15 43 Software Version 15 45 Actual Typecode String 15 49 SW ID Control Card 15 50 SW ID Power Cord 15 60 Option Mounted 15 61 Option SW Version 16 Short ci...

Страница 5: ...ing is issued The frequency converter is still operational but since the brake transistor has short circuited substantial power is transmitted to the brake resistor even if it is inactive Remove power...

Страница 6: ...rd The problem could be on the power card on the gate drive card or the ribbon cable between the power card and gate drive card 40 Overload of digital output terminal 27 Check the load connected to te...

Страница 7: ...r Speed High Limit RPM the frequency converter will show a warning When the speed is below the specified limit in 1 86 Trip Speed Low RPM except when starting or stopping the frequency converter will...

Страница 8: ...ower card temperature The temperature sensor on the power card is either too hot or too cold Check that the ambient operating temperature is within limits Check for clogged filters Check fan operation...

Страница 9: ...ller had entered fire mode Cycle power to the unit to remove the warning See the fire mode data in the alarm log on the controller 202 Fire mode limits exceeded While operating in fire mode one or mor...

Страница 10: ...shorts or incorrect connections If the display continues to cut out follow the procedure for display dark Motor not running Service switch open or missing motor connection Check if the motor is connec...

Страница 11: ...ck brake parameters Check ramp time settings Check parameter group 2 0 DC Brake and 3 0 Reference Limits Open power fuses or circuit breaker trip Phase to phase short Motor or panel has a short phase...

Страница 12: ...e makes noise or vibrations at certain frequencies Resonances for example in the motor pump system Bypass critical frequencies by using parameters in parameter group 4 6 Speed Bypass Check if noise an...

Отзывы: