PAGE 9
Aquavar Intelligent Pump Controller
CentriPro
Warning/Alarm
Description
Cause
Remedy
96 — Start delayed
Motor start has been delayed due to
short-cycle protection.
[22–76] Interval between Starts is
enabled.
Troubleshoot the system and reset
the frequency converter after the fault
has been cleared.
97 — Stop delayed
Stopping the motor has been delayed
due to short cycle protection.
[22–76] Interval between Starts is
enabled.
Troubleshoot the system and reset
the frequency converter after the fault
has been cleared.
98 — Clock fault
Time is not set or the RTC clock has
failed.
Reset the clock in [0–70] Date and
Time.
200 — Fire mode
This indicates the frequency
controller is operating in fire
mode.
Cycle power to the unit to remove the
warning. See the fire mode data in
the alarm log on the controller.
201 — Fire mode was active This indicates the frequency controller
had entered fire mode.
Cycle power to the unit to remove the
warning. See the fire mode data in
the alarm log on the controller.
202 — Fire mode limits
exceeded
While operating in fire mode one
or more alarm conditions has been
ignored which would normally trip the
unit.
Operating in this condition voids
unit warranty.
Cycle power to the unit to remove the
warning. See the fire mode data in
the alarm log on the controller.
203 — Missing motor
With a frequency converter operating
multi-motors, an underload condition
was detected.
This could indicate a missing
motor.
Inspect the system for proper
operation.
204 — Locked rotor
With a frequency converter operating
multi-motors, an overload condition
was detected.
This could indicate a locked rotor. Inspect the motor for proper
operation.
250 — New spare part
A component in the frequency
converter has been replaced.
Reset the frequency converter for
normal operation.
251 — New typecode
A component in the frequency
converter has been replaced and the
typecode changed.
Reset the frequency converter for
normal operation.