UPS Management
The single-line text has the following format:
[Date / Time];[Keyword];[Alarm Text]
where:
[Date / Time] is the date and time of the instant the web page was created
[Keyword] is NORMAL, INFORMATION, WARNING or CRITICAL, indicating increasing severity of the
UPS condition.
[Alarm Text] is a comma separated value (no blanks) of all active alarm conditions
UPS Load Alert
The SNMP/Web adapter monitors the UPS Output Percent Load and reports a UpsLoadAlert when the load drops
of a defined percentage (the actual load step detected is also saved in the UPS log).
This functionality warns the user that there has been a drop in the UPS load. This could indicate potential issues
with the UPS load (fuse blown, breaker tripped, unit off, etc.). Per current implementation, the alert is only avail-
able for HTTP based monitoring.
The following commands (available over the command-line interface – local console or telnet) have been intro-
duced to control this functionality.
Command
Parameters
Description
load_alert_thres
[-1 | 5..100]
This command controls the UPS Load Alert. The UPS output per-
cent load is monitored, and when the drops is above the specified
threshold is will report a UpsLoadAlert condition.
The parameter is expressed in percentage of the UPS rating: the
threshold can be set to a value between 5% and 100%.
Setting it to –1 disables the functionality.
Default value: 15%
load_alert_time
[-1 | 1..500]
This command controls the time that the SNMP/Web adapter will
maintain active the UpsLoadAlert notification. Once the config-
ured time is expired the notification is reset.
The parameter is expressed in minutes: it can be set to a value
between 1 and 500 minutes.
Setting it to –1 means that the notification will never be reset.
Default value: 15 minutes
Note
: when this value is set, the UpsLoadAlert is reset if active.
load_alert_filter
[1..5]
This command controls a filtering and averaging mechanism ap-
plied on the UPS output percent load measurement. This mecha-
nism aims to prevent reporting false conditions following transient
conditions.
The parameter can be set to a value between 1 and 5, where 1 is
no filtering/averaging and 5 is highest filtering.
Default value: 3
Note
: it is not recommended to change this setting.