UPS Management
NOTE:
When using the local serial connection, make sure that the terminal emulation is set to VT-100, otherwise
the interactive menu may not be rendered correctly.
Caution! Some of these commands (particularly upscontrol and upsconfig) may inject commands and/or alter the
UPS configuration with consequences on the UPS operation that may affect the load. Make sure you fully under-
stand the effect on the UPS and on the load before injecting any of these commands. Make sure that it is safe to
perform the desired operation for both the UPS and the load.
Rccmd command group
The rccmd command group allows to configure the RCCMD Server embedded in the SNMP/Web adapter.
Command
Sub-command
Parameters
Description
showrccmd
Shows the current RCCMD Server configuration
rccmd
on|off
Enable/disable Network Shutdown function
on
Network Shutdown enabled
off
Network Shutdown disabled)
add
[ip]
[port]
[cond]
Add an RCCMD Client
[ip]
IP-address of the trap target
[port] Port on which the client is listening
[cond] Shutdown condition:
aXX
after XX minutes on battery
bXX
at XX min remain batt time
test
[num]
Send an RCCMD test message to a specific
RCCMD client
[row] RCCMD client reference
del
[num]
Delete an RCCMD Client
[row] RCCMD client reference
Events command group
The events command group controls the alarm notification via traps and/or e-mail.
Command
Parameters
Description
showevents
Show the alarm notification configuration
event
[row]
[e-mail]
[trap]
[en]
Configure the alarm notification for a specific event
[row] Alarm ID
[e-mail] 0 = no e-mail notification for this alarm
1 = send e-mail on alarm (de)activation
[trap] 0 = no trap sent for this alarm
1 = send trap on alarm (de)activation
[en]
0 = alarm handling disabled
1 = alarm handling enabled
NOTE:
When the specific alarm handling is disabled, the alarm occurrence will be totally filtered – the alarm will
never appear active, it will not be reported by any mean and it will not be logged.