Xtreme Power Conversion Corporation
TX91 3.8- 10kVA User’s Manual
Page 27
Uninterruptible Power Supply
12: Hot standby function enable/disable
Interface
Setting
Parameter 2: HS.H
Enable or disable Hot standby function. You may choose following two op
-
tions in Parameter 3:
YES: Hot standby function is enabled. It means that the current UPS is set to
host of the hot standby function, and it will restart after AC recovery even
without battery connected.
NO: Hot standby function is disabled. The UPS is running at normal mode
and can’t restart without battery
13: Battery voltage adjustment
Interface
Setting
Parameter 2: Select “Add” or “Sub” function to adjust battery voltage to
real figure.
Parameter 3: the voltage range is from 0V to 5.7V, the default value is 0V.
14: Charger voltage adjustment
Interface
Setting
Parameter 2: you may choose Add or Sub to adjust charger voltage
Parameter 3: the voltage range is from 0V to 9.9V, the default value is 0V.
NOTE:
*Before making voltage adjustment, be sure to disconnect all batteries first
to get the accurate charger voltage.
*We strongly suggest using the default value (0). Any modification should
be suitable to battery specifications.
15: Inverter voltage adjustment
Interface
Setting
Parameter 2: you may choose Add or Sub to adjust inverter voltage
Parameter 3: the voltage range is from 0V to 6.4V, the default value is 0V.