XPRT-6kVA, XPRT-10kVA USER’S MANUAL
UNINTERRUPTIBLE POWER SUPPLY (UPS)
Xtreme Power Conversion® (XPC) Corporation (Rev 2/7/13)
Page 64
Batteries
The service life of the batteries in this UPS and BP is from 3 to 5 years, depending on the operating
temperature and number of discharge cycles.
A healthy battery is critical to the performance of the UPS. An automatic quick battery test is performed
regularly to ensure failsafe operation. When the condition of the battery is critical, a REPLACE BATTERY
alarm will be activated. Replace the batteries as soon as possible.
General Guidelines:
•
When replace the batteries, use all the same type and size.
•
Never short the battery terminals. Shorting may cause the battery to
burn. When working with batteries, remove watches, rings or other
metal objects, and only use insulated tools.
•
Avoid charging batteries in a sealed container.
•
Proper disposal of batteries is required. Refer to your local codes for
disposal requirements.
•
Never dispose of batteries in fire - they may explode.
•
Never dismantle or reassemble batteries - their contents (electrolyte)
may be extremely toxic. If exposed to electrolyte, wash immediately
with plenty of water. If eye contact occurs, flush with water and contact
a physician.
Internal Battery Replacement – 6kVA Model
In case of battery failure, please proceed with the following steps.
NOTE
During battery replacement the UPS will not be able to support the load if an input
utility failure occurs! It is recommended to switch off the load
before battery
replacement
.
1.
Remove the UPS front cover from the UPS cabinet by gently pulling it out.
2.
Remove the battery grille by loosening the two mounting screws (FIG 69).