XPRT-6kVA, XPRT-10kVA USER’S MANUAL
UNINTERRUPTIBLE POWER SUPPLY (UPS)
Xtreme Power Conversion® (XPC) Corporation (Rev 2/7/13)
Page 62
SNMP Interface Card (Option)
This card allows the data interface to be connected directly to an Ethernet network. The card is fitted
into the SNMP Card Slot. For more information, please refer to the user manual that comes with the
interface card.
EXTENDED RUNTIME
Extended runtime can be obtained by connecting a separate extended battery pack to the UPS. In this
case the UPS must be informed about the new total battery capacity to allow a reliable recalculation of
the available runtime (via UPS Monitoring Software). Depending of the charge condition of the new
batteries the new runtime calculations may temporarily be unreliable.
Additional batteries increase the recharging time for the unit; all other operational information is the
same as for standard models. The following table shows runtimes with up to 3 Battery Packs. 1 Battery
Pack is the normal configuration.
UNIT
LOAD
ESTIMATED RUNTIME IN MINUTES
INTERNAL
BATTERIES
1 BATTERY
PACK
2 BATTERY
PACKS
3 BATTERY
PACKS
4 BATTERY
PACKS
XPRT-
6000
10%
75
156
235
313
391
25%
31
75
115
155
195
50%
14
34
58
82
105
75%
8
22
35
50
65
100%
5
14
25
36
47
XPRT-
10000
10%
107
251
333
494
590
25%
40
100
160
225
290
50%
16
39
66
92
119
75%
10
24
41
58
75
100%
6
17
28
41
54