NXRT
‐
1000,
NXRT
‐
1500,
NXRT
‐
2000,
NXRT
‐
3000
USER’S
MANUALUNINTERRUPTIBLE
POWER
SUPPLY
(UPS)
APPENDIX
A:
EXTENDED
BATTERY
PACK
USER
GUIDE
Estimated
Run
Time
for
UPS
with
Extended
Battery
Packs
MODEL
LOAD
RUNTIME
FOR
QTY
OF
EXTENDED
BATTERY
PACKS IN
MIN.
VA
WATTS
UPS
(1)
EPB
(2)
EPB
(3)
EBP
(4)
EBP
(5)
EBP
NXRT
‐
1000
500
350
23
85
178
268
333
456
1000
700
10
42
79
121
170
226
NXRT
‐
1500
750
525
15
108
214
336
447
639
1500
1050
7
43
84
132
187
250
NXRT
‐
2000
1000
700
28
170
333
521
737
985
2000
1400
14
68
130
202
284
378
NXRT
‐
3000
1500
1050
19
105
204
318
448
599
3000
2100
8
42
81
126
178
237
Note:
for
estimated
run
times
using
more
than
5
EBP’s,
contact
Xtreme
Power
Conversion
at
.
[37]