VIS-IR Thermography Detector Product Guide
Xtralis
36218_A2
16
5. Insert another command
df -h
and press
Enter
, it will be displayed as shown below above the Red line:
Figure 18: ViSM - Check Proper Insertion of SD Card
The above example shows that the SD Card is properly inserted and activated.
If it is not properly installed check and adjust the SD Card fitment in the slot.
Connecting to Computer
The FTD detectors require ViSM software for configuration and management of the detectors. Up to 8
detectors can be connected to a single instance of ViSM. Use a female Ethernet port in junction box for
connection. A gigabit switch can be used to connect multiple detectors to a single Ethernet port in the computer
workstation as shown below:
Figure 19: Connect Multiple Detectors to Single Ethernet Port