VESDA VLC-605 Installation Guide
VESDA by Xtralis
22
www.xtralis.com
8.3
AutoPulse Control Panel Configuration Requirements
This section assumes that the VLC-605 device has been configured successfully as described in section 8.1
above. The AutoPulse control panel will need to include the necessary information for the VLC-605.
The AutoPulse configuration tool “AutoPulse Programmer Unit Software” (version 8.01 or later) is used to
configure the AutoPulse panel.
The necessary procedure is as follows:
a. Create a 4-20 mA ZAM in the configuration.
b. Set device address in configuration to match the DIP-switch setting made in section 6.13.
c. Set device stage 1, stage 2 and stage 3 thresholds as required for specific installation. Refer to chapter
8.4 for threshold requirements.
8.4
VLC-605 Threshold Configuration Requirements
The VLC-605 device Stage 1, Stage 2 and Stage 3 thresholds are set in terms of counts (1-255) as required by
4-20 mA ZAM devices.
The 4-20 mA range has a resolution of 255 steps. This range provides for step one being the highest
sensitivity (0.016%/ft / 0.0524 %/m) and step 255 being the lowest sensitivity (4.08 %/ ft / 13.39 %/ m). Each
of the 255 steps increment by 0.016 %/ft or 0.0524 %/ m obscuration.
The following formula can be used to determine the necessary count (number 1-255) for the desired %/ ft
obscuration for each threshold.
Count = Sp / Res
Where “Count” is the device count (1 – 255), “Sp” is the desired set point (%/ft or %/m) and “Res” is the device
resolution (0.016 %/ ft or 0.0524 %/m).
Example 1: (%/ft Thresholds)
A threshold of 0.3 %/ ft is required for the Stage 2 Threshold. The formula above will be used to determine the
necessary count setting.
Count = 0.3 / 0.016 = 18.75 so the count will be rounded to 19.
The Count value for the ZAM Stage 2 threshold will be set to 19 in the AutoPulse panel configuration.
Example 2: (%/m Thresholds)
A threshold of 2.0 %/m is required for the Stage 3 Threshold. The formula above will be used to determine the
necessary count setting.
Count = 2.0 / 0.0524 = 38.1, the count will be rounded to 38.
The Count value for the ZAM Stage 3 Threshold will be set to 38 in the AutoPulse panel configuration.
The following table demonstrates some typical obscuration values for various count settings.
Count
%/ft
(0.016 / count)
%/m
(0.0524 / count)
Count
%/ft
%/m
1
0.02
0.05
60
0.96
3.10
5
0.08
0.26
140
2.24
7.35
10
0.16
0.52
160
2.56
8.40
15
0.24
0.79
180
2.88
9.45
20
0.32
1.05
200
3.20
10.50
30
0.48
1.57
220
3.52
11.50
40
0.64
2.10
255
4.08
13.40
Table 8-1: Count setting versus threshold values for the VLC-605
Содержание VESDA VLC-605
Страница 1: ...VESDA VLC 605 Installation Guide October 2016 Document 32445 Revision 0 Build A Part Number 30771 ...
Страница 2: ......
Страница 10: ...VESDA VLC 605 Installation Guide VESDA by Xtralis 4 www xtralis com This page is intentionally left blank ...
Страница 12: ...VESDA VLC 605 Installation Guide VESDA by Xtralis 6 www xtralis com This page is intentionally left blank ...
Страница 14: ...VESDA VLC 605 Installation Guide VESDA by Xtralis 8 www xtralis com This page is intentionally left blank ...
Страница 16: ...VESDA VLC 605 Installation Guide VESDA by Xtralis 10 www xtralis com This page is intentionally left blank ...
Страница 26: ...VESDA VLC 605 Installation Guide VESDA by Xtralis 20 www xtralis com This page is intentionally left blank ...
Страница 30: ...VESDA VLC 605 Installation Guide VESDA by Xtralis 24 www xtralis com This page is intentionally left blank ...
Страница 32: ...VESDA VLC 605 Installation Guide VESDA by Xtralis 26 www xtralis com This page is intentionally left blank ...
Страница 34: ...VESDA VLC 605 Installation Guide VESDA by Xtralis 28 www xtralis com This page is intentionally left blank ...
Страница 40: ...VESDA VLC 605 Installation Guide VESDA by Xtralis 34 www xtralis com This page is intentionally left blank ...