Product Guide
VESDA ECO Detector by Xtralis
74
Troubleshooting
17898_05
VSC
Fault
Number
Root cause
In Field
Serviceable
(Y/N)
Fault Solution (Visible within VSC via F1)
2103
Sensor Module Fault
Sensor RAM Error
N
The Sensor assembly suffered an internal memory failure try to reboot. If unable
to clear replace sensor cartridge and re commission
2104
Sensor Module Fault
Sensor configuration error
N
The Sensor assembly suffered an internal software failure try to reboot. If unable
to clear replace sensor cartridge and re commission
2107
Sensor Module Fault
Sensor software fault
N
The Sensor assembly suffered an internal software failure try to reboot. If unable
to clear replace sensor cartridge and re commission
2109
Sensor Module Fault
N
Sensor failure. Replace sensor cartridge and re-commission.
2110
Sensor Module Fault
N
Sensor failure. Replace sensor cartridge and re-commission.