ICAM IFT-P Product Guide
ICAM by Xtralis
iv
www.xtralis.com
Regional Regulatory Requirements and Notices
ULC
Refer to Appendix C for information on ULC wiring requirements.
UL / ULC
l
Special applications sensitivity range is 0.001 %/m – 1.6 %/m (0.0003 %/ft to 0.50 %/ft). (For Special
Application it is required obtain approval from the Local Authority Having Jurisdiction.)
l
Open Area applications sensitivity range is (1.6 %/m – 12.0 %/m) or 0.5 %/ft to 4 %/ft
EN54-20
The product must use a power supply conforming to EN54-4.
The product is compliant with EN54-20 sensitivity requirements provided that the hole sensitivity is better and
transport time is less than the following values:
Class A
0.6% obs/m, 60 secs
Class B
1.6% obs/m, 60 secs
Class C
3.6% obs/m, 60 secs
The product is compliant with EN54-20 flow monitoring requirements provided that the following conditions are met:
l
Flow Low and Flow High parameters should be set to 85% and 115% respectively for ICAM IFT-P detectors.
Additional Information
Class A, B and C detectors passed EN54-20 approvals testing with the following number of holes and detector
sensitivities:
Class A
12 holes, 0.04% obs/m
Class B
36 holes, 0.04% obs/m
Class C
36 holes, 0.1% obs/m
Listings / Approvals
l
UL
l
ULC
l
FM
l
CCC
l
CE
l
VdS
l
NF
l
EN 54-20
Содержание ICAM IFT-P
Страница 1: ...ICAM IFT P Product Guide February 2017 Document 19317 Revision A Build 1 Part Number 29714 ...
Страница 2: ......
Страница 8: ...ICAM IFT P Product Guide ICAM by Xtralis 2 www xtralis com This page is intentionally left blank ...
Страница 12: ...ICAM IFT P Product Guide ICAM by Xtralis 6 www xtralis com This page is intentionally left blank ...
Страница 22: ...ICAM IFT P Product Guide ICAM by Xtralis 16 www xtralis com This page is intentionally left blank ...
Страница 28: ...ICAM IFT P Product Guide ICAM by Xtralis 22 www xtralis com This page is intentionally left blank ...