13
2.3
Connection of Air Sampling Network
Note:
For more details please refer to the ICAM Pipe Network Installation Manual.
There are several common guidelines that should be followed when attaching the pipe network to the ICAM
IFT-P detector:
l
Pipes must NEVER be glued to the inlets of the detector
l
Pipe network itself MUST be glued together
l
Use removable unions where necessary
Caution:
Do not insert ANY object into the inlet ports other than the correct size of piping. This is to avoid
damage to delicate electronic flow sensor components mounted just inside each port opening.
Attention :
N'insérez AUCUN objet dans les entrées d'admission, sauf le tube de dimension appropriée.
Ceci permet d'éviter d'endommager les composants électriques délicats fixés juste à l'entrée de
chaque tube.
Other pipe and inlet specifications are addressed in the following table.
Table 2-1: Detector Inlet to Pipe Network Termination Specifications
Detector
Inlet Port
Acceptable Pipe or
Adapter
Maximum Pipe
Length
Other Considerations
ICAM IFT-P
25mm (1in.)
outer-diameter
UPVC tubes
25mm (1in.); or
26.7mm (1.05in.) with 25
(1in.) to 26.7mm
(1.05in.) adaptors
2 x 100m (328ft.)
-
Содержание ICAM IFT-P
Страница 1: ...ICAM IFT P Product Guide February 2017 Document 19317 Revision A Build 1 Part Number 29714 ...
Страница 2: ......
Страница 8: ...ICAM IFT P Product Guide ICAM by Xtralis 2 www xtralis com This page is intentionally left blank ...
Страница 12: ...ICAM IFT P Product Guide ICAM by Xtralis 6 www xtralis com This page is intentionally left blank ...
Страница 22: ...ICAM IFT P Product Guide ICAM by Xtralis 16 www xtralis com This page is intentionally left blank ...
Страница 28: ...ICAM IFT P Product Guide ICAM by Xtralis 22 www xtralis com This page is intentionally left blank ...