ICAM by Xtralis
ICAM IFT-P Product Guide
www.xtralis.com
33
User Functions
User functions associated with some configuration and control buttons are described in this section.
Function
Access Level
Description
ACCEPT
None
Acts only on the internal sounder. Acknowledges all current Alarm states.
All other warning mechanisms continue unchanged. Sounder operation
changes from continuous to 1 second ON: 15 seconds OFF. New Alarm
events cause the sounder to revert to continuous operation.
SOUNDER
SILENCE
Operator
Acts only on the internal sounder. The Sounder is switched off until one or
more new Alarm events.
RESET
Operator
Clears all latched Alarms and Faults. Current Alarms or Faults will remain.
ISOLATE
Operator
Used when diagnosing faults, testing new installations etc. All alarm
relays are disabled, so that Alarm conditions will not be reported back to
the Host Panel. The Isolate button toggles the unit between Isolated and
Normal operation, as shown by the Isolated indicator, but see note below.
Notes:
l
If the unit is isolated then returned to the Normal, Locked state (by
pressing the
MENU
button) the Operator will need to re-enter
Operator Access Code in order to cancel the isolated state.
l
If a power cycle is applied to the detector, the detector will not
remain in an isolated state.
TEST
None
Successive presses of the Test button show:
1. Date on the Status Display
2. Time on the Status Display
3. IP address on the Status Display
4. Subnet net mask on the Status Display
5. Media Access Control (MAC) address on the Status Display
6. All activated LEDs on the panel and LED segments on the Status
Display
7. Normal display
Table D-3: Description of User Functions for the Remote Display Unit
The ICAM IFT-P detector can also be reset remotely by applying 24 VDC to the remote reset input on the
Main I/O PCB. Refer to section 2.2.1 for further information.
Note:
When the Operator Access Code is entered (default = 0), the Sounder Silence, Reset and Isolate
user functions are enabled and the unit is placed in the Unlock state, as shown by the flashing
Unlock indicator. If the unit is isolated, then returned to the Normal, Locked state (by pressing the
Main Menu button) the Operator will need to re-enter Operator Code in order to cancel the Isolated
state. If any button is not pressed to lock the panel the unit will self-timeout and lock in 5 minutes.
Содержание ICAM IFT-P
Страница 1: ...ICAM IFT P Product Guide February 2017 Document 19317 Revision A Build 1 Part Number 29714 ...
Страница 2: ......
Страница 8: ...ICAM IFT P Product Guide ICAM by Xtralis 2 www xtralis com This page is intentionally left blank ...
Страница 12: ...ICAM IFT P Product Guide ICAM by Xtralis 6 www xtralis com This page is intentionally left blank ...
Страница 22: ...ICAM IFT P Product Guide ICAM by Xtralis 16 www xtralis com This page is intentionally left blank ...
Страница 28: ...ICAM IFT P Product Guide ICAM by Xtralis 22 www xtralis com This page is intentionally left blank ...