Environment effections such as ambient temperature, humidity, fog ,internal component aging and other factors will give rise to the occurrence
of potential faults. Therefore, it is necessary to conduct daily check and routine maintenance to the inverters.
6-1-1
6-1-1
6-1-1
6-1-1.... Routine
Routine
Routine
Routine maintenance
maintenance
maintenance
maintenance
Please confirm the following items when start the inverter.
(
1
)
If there is abnormal noise and vibration with th motor.
(
2
)
If the inverter and motor heat unusually.
(
3
)
If the environment temperature is too high.
(
4
)
If the value of load amperometer is as usual.
(
5
)
If the fan of inverter can operate normally.
6-2.
6-2.
6-2.
6-2. Periodical
Periodical
Periodical
Periodical care
care
care
care and
and
and
and ma
ma
ma
maiiiint
nt
nt
nteeeen
n
n
na
a
a
ance
nce
nce
nce
6-2-1
6-2-1
6-2-1
6-2-1.Periodical
.Periodical
.Periodical
.Periodical care
care
care
care
Before check and maintenance the inverter, please make sure that the inverter is power off, monitor has no display content
and the indication lamp of main circuit power is off.The checked contents are shown in Tabel 6-1.
Table
Table
Table
Table 6-1
6-1
6-1
6-1 periodical
periodical
periodical
periodical maintenance
maintenance
maintenance
maintenance
6-2-
6-2-
6-2-
6-2-2.
2.
2.
2. Periodical
Periodical
Periodical
Periodical maintenance
maintenance
maintenance
maintenance
To make the inverter work normally for long time, periodical care and maintenance for inverter’s internal electronic
component should be done. The electronic component’s lifetime depends largely on their application environment and
preservation. Normally, lifetime is:
Items
Contents
Countermeasures
Main
circuit
terminals,
control
circuit terminals
If the screws are loose
Tighten the screws with screw drivers
Heatsink
If there is dust
Use dry compressed air with 4
~
6kgcm
2
pressure
PCB print circuit board
If there is dust
Use dry compressed air with 4
~
6kgcm
2
pressure
Cooling fan
There is abnormal noise, vibration, or if it has run for
more than 20 000 hours.
Change cooling fan
Power component
If there is dust
Use dry compressed air with 4
~
6kgcm
2
pressure
Aluminium electrolytic capacitors
If it has changed color , particular smell or bubble
Change aluminium electrolytic capacitors