40
responsiveness, as an auxiliary parameter.
5-1-2. Recommended inertia ratio under default parameters
Motor
flange
Recommended load inertia ratio
in small inertia mode
Recommended load inertia
ratio in large inertia mode
40
Below 20 times
60 times ~ 80 times
60
Below 20 times
60 times ~ 80 times
80
Below 20 times
60 times ~ 80 times
130
Below 10 times
15 times ~ 20 times
180
Below 5 times
10 times ~ 20 times
If the load inertia is over the recommended value in the table, please change the related
parameters of gain. The method is shown as below:
If the inertia is 20 times to 30 times
Increase P2-07 appropriately, decrease P2-05 if necessary. You can also refer to the following
super-large inertia debugging methods.
Super-large debugging experience (50-100 times inertia):
Increase P2-12 (40~50 is recommended), reduce P2-08 (40~50 is recommended), reduce
P2-05(100~300 is recommended), increase P2-07(10~50 is recommended). Please flexible
adjust according to load inertia.
Application example:
(1)
30-times inertia load gain parameters
When it is default value, please set P2-08=50 P2-12=40 P2-07=50
(2)
80-times inertia load gain parameters
When it is default value, please set P2-08=40 P2-12=50 P2-07=50 P2-05=200
Содержание DS5C Series
Страница 1: ...DS5C series servo driver Fast manual Version 1 Wuxi Xinje Electric Co Ltd Data No SC502 20181025 1 0...
Страница 3: ......
Страница 4: ......
Страница 13: ...5 1 2 Servo motor 1 2 1 Part description Encoder part Frame Flange Output transmission shaft...
Страница 29: ...21 2 4 Servo drive dimension Unit mm DS5C 20P1 2 4 PTA 45 0 175 0 175 1 178 0 164 0 33 8 5 5 5 5...
Страница 30: ...22 DS5C 20P7 PTA 60 0 183 0 181 3 48 8 172 0 5 5 5 5 182 9...
Страница 54: ...46...
Страница 120: ......