Orientation
4
)
Installation
Follow the procedure below to install multiple servo drives side by side in a control panel.
CHARGE
POWER
ENTER
DEC
INC
ESC
STA
STA
ESC
INC
DEC
ENTER
POWER
CHARGE
CHARGE
POWER
ENTER
DEC
INC
ESC
STA
STA
ESC
INC
DEC
ENTER
POWER
CHARGE
Servo drive Orientation
Install the servo drive perpendicular to the wall so the front panel containing connectors
faces outward.
Cooling
As shown in the figure above, allow sufficient space around each servo drive for
cooling by cooling fans or natural convection.
Side-by-side Installation
When install servo drives side by side as shown in the figure above, make at least 10mm
between and at least 50mm above and below each servo drive. Install cooling fans above the
servo drives to avoid excessive temperature rise and to maintain even temperature inside the
Install the servo drive perpendicular to the wall as
shown in the figure. The servo drive must be
oriented this way because it is designed to be cooled
by natural convection or by a cooling fan.
30mm minimum
50mm minimum
50mm minimum
10mm minimum
Wall
Ventilation