Faults and Warnings
975-0240-01-01
4–23
F47
DC Under Voltage
Automatic
DC under-voltage
shutdown (immediate)
occurs if DC voltage is
below 16 Vdc (24 V) or
32 Vdc (48 V)
The fault clears and the
inverter restarts when
DC voltage reaches
23 Vdc (24 V) or 46 Vdc
(48 V).
Check for the correct battery voltage
at the inverter’s DC input terminals.
Check for an external DC load on
the batteries. Check condition of
batteries and recharge if possible.
F48
DC Under Voltage
Automatic
DC under-voltage
shutdown occurs if DC
voltage is below 20 Vdc
(24 V) or 44 Vdc (48 V).
See F47.
F49
DC Over Voltage
Automatic
DC over-voltage
shutdown. Occurs if DC
voltage is above 32 Vdc
(24 V) or 70 Vdc (48 V).
Clear the fault and attempt restart.
Ensure battery voltage is below
29 Vdc (24 V) or 58 Vdc (48 V) at
XW Inverter/Charger terminals.
Check all other charging source
outputs, battery cables. Ensure your
DC source is regulated below your
high battery cut out or increase your
Hi Batt Cut Out
setting.
F52
EEPROM Error
Manual
No action. Clear fault and resume
operating or configuring the unit. If
the fault persists, have the unit
serviced.
F53
EEPROM Error
Manual
See F52.
F54
EEPROM Error
Manual
See F52.
F55
EEPROM Error
Manual
See F52.
F56
EEPROM Error
Manual
See F52.
Table 4-5
Fault Messages
Fault
Number
Message
Fault Type
Cause
Solution