Operation
Using the Shutdown Function
Revision A
69
Table 3.4
Relay and Switch Settings for Contact Closure
The red S/D (Shutdown) LED on the front panel lights up when the Shutdown circuit
is activated.
Figure 3.19
Using Shutdown with Contact Closure of a Normally OPEN Relay
(Positive Logic)
Relay
Switch SW1-8 Setting
Relay Coil State
Output
Normally Open Relay
OPEN (Positive Logic)
Energized
OFF
De-energized
ON
CLOSED (Negative Logic)
Energized
ON
De-energized
OFF
Normally Closed Relay
OPEN (Positive Logic)
Energized
ON
De-energized
OFF
CLOSED (Negative Logic)
Energized
OFF
De-energized
ON
RELAY COIL DE-ENERGIZED = OUTPUT ON
(AS SHOWN)
RELAY COIL ENERGIZED = OUTPUT OFF
RELAY
NORMALLY OPEN
15
6
2
14
1
25
13
J3
OPEN (OFF)
CLOSED (ON)
2
3
4
5
6
7
8
1
SW1
JMP2
A
B
C