Operation
Remote Programming of Output Voltage and Current Limit
Revision A
57
Programming
Output
Voltage
Programming Output Voltage with a 0-5Vdc Source
1. Remove the jumpers connecting pins 8 to 9 and 20 to 21 on connector J3.
2. Connect the external programming source between pins 9 (voltage
programming input/positive) and 12 (return).
Varying the programming voltage from 0 to 5Vdc will cause the output to vary from
0 to 100% of the model rating. The output current limit may be programmed using
another source or set locally by adjusting the front panel current limit control.
Figure 3.5
Programming Output Voltage with a 0-5Vdc Source
Programming Output Voltage with a 0-10V Source
1. Set internal jumper JMP1 to its A-B location.
2. Remove the jumpers connecting pins 8 to 9 and 20 to 21 on connector J3.
3. Connect the external voltage programming source between pins 9 (voltage
programming input/positive) and 12 (return).
Varying the programming voltage from 0 to 10Vdc will cause the output voltage to
vary from 0 to 100% of the model rating. The output current limit may be
programmed using another source or set locally by adjusting the front panel current
control.
Note:
Resetting internal jumpers may require a recalibration of the programming circuit to
maintain programming accuracy. See
“Calibrating for Programming Accuracy” on
page 82
.
J3
+
0 - 5 V
WARNING
Exercise caution when resetting internal jumpers. Follow the procedures for
removing the cover and resetting jumpers in
“Configuring for Remote
Programming, Sensing, and Monitoring” on page 48
.
TM-25OP-01XN.book Page 57 Monday, April 5, 2004 8:58 AM
Содержание XKW 12-150
Страница 2: ......
Страница 3: ...Operating Manual for XKW 3000 Watt Series Programmable DC Power Supply...
Страница 14: ...xii Operating Manual for XKW 3kW Series Power Supply...
Страница 18: ...List of Tables xvi Operating Manual for XKW 3kW Series Power Supply...
Страница 28: ...Features and Specifications Specifications 26 Operating Manual for XKW 3kW Series Power Supply...
Страница 48: ...Installation Using Remote Sensing 46 Operating Manual for XKW 3kW Series Power Supply...
Страница 80: ...Operation Using Multiple Supplies 78 Operating Manual for XKW 3kW Series Power Supply...
Страница 89: ......