Features and Specifications
Specifications
28
Operating Manual for XFR 1.2kW Series Power Supply
Additional
Specifications
Input
Conditions
Rise Time (No Load, Full Load):
1
6 V to 60 V models: 100 ms;
100 V to 600 V models: 170 ms
Fall Time (No Load):
1
6 V model: 1.5 s;
7.5 V to 60 V models: 3 s;
100 V to 600 V models: 4 s
Fall Time (Full Load):
1
6 V model: 10 ms;
7.5 V to 60 V models: 100 ms;
100 V to 600 V models: 170 ms
Voltage Mode Transient Response:
2
<3 ms
Time Delay from power on until
output stable
7 s maximum
1. Measured with stepped 0-10 V analog programming source and a resistive load.
2. Time for the output voltage to recover within 0.5% of its rated value after a step change
in load current of 10% to 90% of rated output with an output setpoint between 50-100%
of rated value. Load slew rate <6 A/ms.
Rated AC Input Voltage
100/120/200/220/230/240 Vac (nominal) ±10%
Maximum AC Input Power
2600 VA
Operational AC Input Voltage
85-130 Vac or 190-264 Vac, 1
φ
;
6 V model: 95-130 Vac or 190-264 Vac, 1
φ
.
Auto range select function.
Maximum Input Current
20 A maximum at 120 Vac,
12 A maximum at 230 Vac.
Input Frequency Range
47-63 Hz
Power Factor
0.65 minimum at full load and 100 Vac input;
0.55 minimum at full load and 200 Vac input.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com