4.0 TROUBLESHOOTING
©2000 Xantrex Technology Inc.
Troubleshooting
Error Condition
Possible Cause
Solution
No AC output and no warning
LEDs are ON.
Battery voltage at the inverter
terminals is too high or low.
Check the battery voltage, fuses or breakers,
and cable connections.
AC output is low and the inverter
turns loads ON and OFF.
Low battery.
Check the condition of the batteries and
recharge if possible.
Replace the batteries.
AC output is low.
Loose or corroded battery
connections.
Loose AC output connections.
Check and clean all DC connections.
Check all AC output connections.
AC output voltage is low.
Measuring AC output with incorrect
type of meter.
AC output voltage low using a true
rms reading meter or DVM.
Measure AC output voltage with a true rms
reading meter or DVM.
Have unit serviced.
CHARGER LED:
- indicates charging, but no
charge is going to the batteries.
- is ON, but there is no output
power.
Circuit breaker on the side of the
inverter is open.
No AC voltage on inverter’s AC
terminal block.
Good AC voltage on inverter’s AC
terminal block.
Reset the AC CHARGER circuit breaker on
the side of the unit.
Check "AC PASS-THRU" circuit breaker on
the side of the inverter.
Check for open AC output breakers or fuses
and AC wiring connections.
Charger is inoperative or
supplying a low charge rate.
AC voltage has dropped out-of-
tolerance.
Charger controls are improperly set.
Low peak AC input voltage (169
VAC
p
required for full charger
output).
AC current supplied from generator
is too low.
Loose or corroded battery
connections.
Loose AC output connections.
Generator is unstable - charger is
losing synchronization.
Check the AC voltage for proper voltage and
frequency (depending upon model).
Refer to the section on adjusting the
"CHARGER RATE."
Use larger generator (increasing AC
voltage/RPM’s may help).
Reduce charge amps setting or reduce pass-
through loads.
Check and clean all DC connections.
Check all AC output wiring connections.
Turn BATTERY CHARGER RATE
potentiometer down to less than halfway until
problem is gone.
AC lights flicker while charging.
Generator is unstable and charger
is losing synchronization.
Turn BATTERY CHARGER RATE
potentiometer down to less than halfway until
problem is gone.
Charger turns OFF while charging
from a generator.
High peak AC input voltages from
the generator.
Load the generator down with a heavy load.
Turn the generator output voltage down.
975-0012-015B