SECTION 5
TROUBLESHOOTING
DOCUMENT: 151710
PV-45208 Photovoltaic Inverter
Operation and Maintenance Manual
Copyright 2002, Xantrex Technology Inc.
5-1
GENERAL
In the event of a fault, the PV-45208 will annunciate the condition at the operator interface. The PV-
45208 will execute an orderly shutdown and remain faulted until the fault is cleared (manually or auto-
matically).
In general, the operator should respond to any PV-45208 fault as follows:
1. The source of the fault should be sought by referring to the following chart.
2. Rectify the fault condition and attempt to clear the fault by cycling the on/off switch.
3. If the problem cannot be corrected, note and write down the fault code and description, then contact
your Xantrex Technology distributor for assistance or service.
FAULT CONDITIONS
LCD Fault Annunciation
The LCD interface reports fault conditions on Line 2 and 3. The fault code number will follow a text
description. The fault description will remain displayed until the fault has been corrected and cleared.
Each fault is described on the following page.
Fault Clearing
Faults may be cleared automatically by the PV-45208 or manually by the operator depending upon the
type of fault. The utility protection faults (over/under AC line voltage and frequency) are self-clearing
fault conditions. Once the utility voltage and frequency returns within allowable operating ranges, for a
period of five minutes, the PV-45208 will clear the fault and resume normal operation.
Latching faults must be cleared manually by the system operator.
Once the cause of the fault condition
has been corrected, the fault may be cleared with the on/off switch. First turn the switch to the off
position and then back to the on position in order to reset the inverter. If a fault is sustained, the inverter
will not reset, and will continue to report the fault. If the fault has been corrected, the LCD will return to
the normal display, and the PV-45208 will resume normal operation.
LCD Display and On/Off Switch