Output Power Versus Ambient Temperature
975-0320-01-01
A–3
Adjustable Voltage, Frequency and Reconnection Settings
Utility disconnect settings can be adjusted using the GTConfigLite software tool.
Permission of the utility must be granted before adjusting any of these settings.
For more information about installing and using GTConfigLite, see the
GTConfigLite User’s Guide
(p/n 976-0260-01-01), available on the software CD.
Output Power Versus Ambient Temperature
Once the heat sink on the inverter reaches a maximum temperature limit, the GT
Inverter reduces its energy output to ensure maximum component ratings are not
exceeded.
Setting
Default
Range
Tolerance
Phase-to-phase (rms) high threshold voltage
261.00
261.00–264.00
±3 V
Phase-to-phase (rms) low threshold voltage
214.00
204.00–214.00
Phase-to-neutral (rms) high threshold voltage
130.50
130.50–132.00
±1.5 V
Phase-to-neutral (rms) low threshold voltage
107.10
102.00–107.10
Frequency high threshold
60.40
60.40–60.60
±0.1 Hz
Frequency low threshold
59.40
57.00–59.80
Voltage (rms) High Clearing Time (ms)
<1000
1000–2000
+0, –0.1 s
Voltage (rms) Low Clearing Time (ms)
<2000
2000–5000
Frequency High Clearing Time (ms)
<160
160–200
Frequency Low Clearing Time (ms)
<160
160–300000
Reconnect Delay (ms)
305000
60000–305000
n/a
Figure A-1
Output Power vs. Ambient Temperature
GT5 Output Power Derating vs Ambient Temperature @ 550VDC
0
1000
2000
3000
4000
5000
25
30
35
40
45
50
55
60
65
70
Temperature (C)
Ou
tp
u
t P
o
we
r (
W
)
Содержание GT5.0-NA
Страница 1: ...Grid Tie Solar Inverter Xantrex Grid Tie Solar Inverter Owner s Manual GT5 0 NA ...
Страница 2: ......
Страница 3: ...Xantrex Grid Tie Solar Inverter Owner s Manual ...
Страница 8: ...vi ...
Страница 14: ...xii ...
Страница 18: ...1 4 ...
Страница 48: ...4 6 ...
Страница 60: ...5 12 ...
Страница 70: ...6 10 ...
Страница 76: ...A 6 ...
Страница 83: ......