Specifications
A–2
975-0320-01-01
Electrical Specifications
Input
Output
Input voltage, Maximum Power Point range
240 to 550 Vdc
Absolute maximum array open circuit voltage
600 Vdc
Maximum input current
22.0 Adc
Maximum array short circuit current
24 Adc
Reverse polarity protection
Short circuit diode
Ground fault protection
GF detection, I
DIF
> 1 A
Maximum output power
5000 W AC
Nominal output voltage
240 V
Operating range, utility voltage*
*
Factory settings can be adjusted with the approval of the utility. This
unit is provided with adjustable trip limits and may be aggregated
above 30 kW on a single Point of Common Coupling. See “Adjustable
Voltage, Frequency and Reconnection Settings” on page A–3.
211 to 264 Vac
Nominal output frequency
60 Hz
Operating range, utility frequency*
59.3 to 60.5 Hz
Startup current
0 Aac
Maximum continuous output current
21 A
Output overcurrent protection
30 A RMS
Maximum utility backfeed current
0 A
Total Harmonic Distortion
<5%
Power factor
>0.95%
Utility monitoring— islanding protection
Vac, fac as per UL 1741 (2005)
Output characteristics
Current source
Output current waveform
Sine wave
Содержание GT5.0-NA
Страница 1: ...Grid Tie Solar Inverter Xantrex Grid Tie Solar Inverter Owner s Manual GT5 0 NA ...
Страница 2: ......
Страница 3: ...Xantrex Grid Tie Solar Inverter Owner s Manual ...
Страница 8: ...vi ...
Страница 14: ...xii ...
Страница 18: ...1 4 ...
Страница 48: ...4 6 ...
Страница 60: ...5 12 ...
Страница 70: ...6 10 ...
Страница 76: ...A 6 ...
Страница 83: ......