Basic Installation Procedures
975-0395-01-01
1–23
This guide for use by qualified installers only
In this wiring diagram, the AC input to the
Freedom HF
comes directly
from an AC source. The AC source input wiring must be protected by an
AC breaker of 30 A max. The output wiring is routed to the main AC
panel which is also protected by AC breakers or circuit breakers.
Figure 1-7
AC Wiring Diagram without an Inverter Subpanel
Input breakers must
be provided by
installers.
See Important note below.
See Important
note below.
CAUTION: Equipment damage
Do NOT connect the AC OUT Neutral and Line
to the AC IN Neutral and Line.
Important:
The generator must have its neutral bonded to ground. If it is not
bonded, a bonding jumper must be installed between the neutral and ground at
the generator’s output or at the generator side of the transfer switch.
Also, the main AC panel must not have a permanent neutral to ground bond
installed.