This guide for use by qualified installers only
Connecting the Equipment Ground
The
Freedom HF
has a ground stud on the side of the unit as shown in
Figure 1-4
. Follow the guidelines in
“Grounding Locations”
to connect
the inverter’s chassis to the ground.
Grounding Locations
You must connect the equipment ground stud to a grounding point—
usually the vehicle’s chassis or DC negative bus ground—using
recommended copper wire (if insulated then green insulation with or
without one or more yellow stripes) or larger.
For recommended equipment ground cable size, see below.
In general, the equipment ground cable size must not be smaller than one
AWG size than the supply cable.
WARNING: Fire hazard
Never operate the
Freedom HF
without properly connecting the equipment
ground. A fire hazard could result from improper grounding.
Figure 1-4
DC Panel Connections
Equipment
ground stud
Table 1-3
Recommended Equipment Ground Cable size
Application
Minimum equipment ground cable size
(Stranded cable is recommended)
Recreational Vehicle
a
a.Based on US National Electrical Code NFPA70, Article 551, par. 551-20c 2005
version.
No. 8 AWG
Marine
b
b.Based on ABYC E-11 11.18 dated 07/03
No. 3 AWG (
Freedom HF 1000
)
No. 1/0 AWG (
Freedom HF 1800
)
Note
: There are no restrictions on length for the equipment ground cable.
FreedomHF_IC_01-Installation.fm Page 14 Monday, December 24, 2007 9:47 AM
Содержание FREEDOM HF 1000
Страница 2: ...Freedom HF Install Guide book Page ii Friday December 21 2007 9 57 PM...
Страница 56: ...2 6 FreedomHF_IC_02 Configuration fm Page 6 Monday December 24 2007 9 48 AM...
Страница 64: ...A 8 FreedomHF_IC_A Specifications fm Page 8 Monday December 24 2007 9 48 AM...
Страница 68: ...B 4 Freedom HF Install Guide book Page 4 Friday December 21 2007 9 57 PM...
Страница 69: ...Freedom HF Install Guide book Page 5 Friday December 21 2007 9 57 PM...