Parallel Installation Steps
975-1044-01-01
15
6. Then connect the battery positive cable from the second Rebling
connector to the common positive bus.
NOTE
: If more than two batteries are being connected, ensure a
consistent connection method is used for connecting the batteries.
7. Connect the battery negative terminal from the first Rebling connector to
the common negative bus.
8. Then connect the negative positive cable from the second Rebling
connector to the common negative bus.
NOTE
: If more than two batteries are being connected, ensure a
consistent connection method is used for connecting the batteries.
9. Install your DC-rated circuit protection device in line with the common
positive bus.
NOTE
: In parallel installations, one DC-rated protection device may
protect only two batteries as shown. In the case of a third or fourth
battery, a second protection device must be installed.
10. Connect the final connection cables from the common negative bus to
its termination point on the charging device and from the remaining
positive terminal of the DC-rated circuit protection device to its
termination point on the charging device.
11. Attach the cable-mounted keyable plug to the battery terminals of the
first battery by turning the key lever clockwise. Do the same for the
second battery.
12. Double check all connections for any reverse wiring or incorrectly connected batteries.
13. Ensure all battery terminals are torqued correctly according to specifications.
NOTE
: Double check all your wiring between batteries for any reversed cables. Check the DC protection device/s for the
correct polarity as well.
14. Turn ON all the batteries using the power push button on the battery.
NOTE
: Wait for all batteries to be fully turned on before proceeding to connect to the main system by closing the DC
disconnect or DC breaker. You may observe that when one battery is turned on, other connected batteries will be
activated as well.