SI 675
Issue B
EDI 8262
Telescopic cranes with derrick pressure sensors CALIBRATION W2245
16
The calibration mode is organized into a logical sequence. A series of some 27
items or sections will appear. The ROLL UP (#2) or ROLL DOWN (#4) button
allows the technician to scroll through these items. Although once in the
calibration menu it is possible to scroll and access any stage of the calibration, it is
recommended to follow the progressive order as described in this manual. This
will prevent calibration of stages with non-calibrated pre-requisite stages.
The sequence for calibration is shown below
1
=
Calibration enable/disable
2
=
Zero Angle
3
=
Span Angle
4
=
Zero Extension
5
=
Span Extension
6
=
zero pres Bore
7
=
zero pres Rod
8
=
span pres bore
9
=
span pres Rod
10 =
Boom Cfg#1
11 =
No Deduct
12 =
No Rooster H
13 =
Part Line : 3
14 =
Tare Load : 0.0
15 =
P1 : 20º retract
16 =
P2 : 60º retract
17 =
P3 : 60º 1/3 Ex
18 =
P4 : 60º FullEx
19 =
Boom Moment
20 =
Cal Load : 0.0
21 =
Load Bend Corr