Telescopic cranes with derrick pressure sensors CALIBRATION W2245
17
22 =
Load Adjust
23 =
Backup
24 =
Memory
25 =
Calib. Data
26 =
Dimensions
27 =
Config Menu
4.2.1 Enquiry Mode:
It is possible to enter the calibration mode to look at the settings made
without having to open the display unit. Hold down button 1 and press
buttons 3 and 4 simultaneously, then release all three buttons at the same
time. The system will enter the calibration mode but no access will be
allowed to change anything. Exit by pressing buttons 7 and 8 simultaneously
(Reset).
4.2.2 Calibration Mode:
To enter calibration, turn the system on, wait until the system shows the
basic screen with load, angle, etc. Then move the calibration switch(on the
I/O board) to the CALIBRATION MODE position.
The display will show:-
The system is now in the calibration mode.
By pressing the buttons DOWN (#4) or UP (#2), it is possible to scroll
through the calibration menu.
4.2.3 Return to Normal Operating Mode
To leave the calibration mode and return to the normal operating mode,
simply move the calibration switch, on the I/O board, to the NORMAL MODE
position. The system will automatically reset and return to the normal
operating mode.
If the system was configured during calibration E.G.: Main winch, 4 falls,
Main boom only, it will not retain that configuration and will instead return to
the last configuration set during operating mode.
4.2.4 Password Access
Calib:#2
↑
- #4
↓
1 – Calib Disable
Calib:#2
↑
- #4
↓
1 – Calib Disable