FKE003

 

 
 

Product information 

 

FKE003_V2.2_PI_2018-01_EN 

Subject to technical changes 

Page 5 of 8 

P

1

2

Display and control elements 

 

 3 

 

 

 

 

4 Device 

operation 

The setting menu is divided into 2 distinct function areas, the 

standard level and the advanced level

The 

standard level

 encompasses only the display of the control actual value and the status LEDs. 

The 

advanced level

 encompasses all parameters (P01 to P16). 

4.1 

Activating the advanced level 

1.  To switch to advanced level, press the <P> key for 5 seconds. 

The LED "Advanced level" will flash for as long as the level is released. 

P

 

...

      

P

 

...

 

 5s

 

2.  To return to the advanced level, press the <P> key again for 5 seconds. 

If no key is pressed within 2 minutes, the display automatically returns to the standard level. 

4.2 Selecting 

parameters 

1.  Press the <P> key to display the parameter number. 

The parameter number will appear in the display for as long as the key is depressed. 

2.  To select individual parameters with the <P> key depressed, press the 

 or

 key. 

When the keys are released, the value corresponding to the parameter is displayed. 

P

      

P

      

P

      

P

 

 

 

 

 

 

 

 

LEDs and 7-segment display 

Parameter change approved 

2 Advanced 

level 

3 Status 

LEDs 

Value / parameter number 

 

Display symbols 

Defrosting 
Cooling 
Fan 

Содержание FKE003

Страница 1: ...ctronic relay valve controller 230V or ATV230 valve actuation 230V Control of one evaporator per module Integrated temperature display Tool free front installation Fixed input output allocation for se...

Страница 2: ...ric shock and or fire Switch off the power to the entire plant when installing wiring or removing Otherwise a mains voltage and or external voltage may still be present even if the control voltage is...

Страница 3: ...rol elements 5 4 Device operation 5 4 1 Activating the advanced level 5 4 2 Selecting parameters 5 4 3 Set parameter 6 4 4 Set module number 6 4 5 Block keys against unauthorised operation 6 5 Paramet...

Страница 4: ...for the FKE003 Cables Application ZCB C TR 0 6 Controller transformer 0 6m ZCB C TR 2 0 Controller transformer 2 0m ZCB C REL2M 5P Controller load 5 pin ZCB C DI 2 0 Controller digital inputs 2 0m ZC...

Страница 5: ...Advanced level will flash for as long as the level is released P P 5s 2 To return to the advanced level press the P key again for 5 seconds If no key is pressed within 2 minutes the display automatic...

Страница 6: ...ed within 2 minutes the display automatically returns to the standard level and parameter change is disabled The jump back is always made to the temperature display 4 4 Set module number For easier se...

Страница 7: ...ure of suction gas sensor S4 P05 Actual value 4 20mA 0 25 5 Current on 4 20mA input resolution 0 25 5mA P06 Actual value 0 10V output 0 100 Triggering of the 0 10V output resolution 0 100 P07 Sensor t...

Страница 8: ...d connection supply air return air defrost limit 1 x TRK EEV 7ST suction gas Analogue input 4 20mA output voltage 18V max 22mA Digital inputs 3 x potential free contact 1 x cold location off 1 x 2nd s...

Отзывы: