5-1

5.  Configuration

5.1.  System Mode and User Mode

In order to restrict access to sensitive command functions, the RPC-4850-8N 

features two operating modes; System Mode and User Mode.

• 

System Mode:

  Allows access to all configuration menus, switching 

functions, reboot functions and status screens.  The System Mode Status 

Screens show On/Off conditions for all switched circuits, and lists all 

currently defined system parameters.

• 

User Mode:

  Allows access to switching and reboot commands, but 

does not allow access to configuration functions.  Users may only issue 

commands to, or view status of the circuits that are specifically allowed 

by their password.

The RPC will display a password prompt when the unit is contacted via 

the Console Port or Network Port.  The password entered at this prompt 

determines whether the unit will start-up in System Mode or User Mode.  If 

the System Password is entered, the System Mode will be active.  If a Circuit 

Password is entered, the User Mode will be active.  The System Password 

is defined via the General Parameters menu (Section 5.3.1), and the Circuit 

Passwords are defined via the Circuit Parameters Menus (Section 5.3.3.)

Notes:

•  If you wish to restrict access to configuration menus, you must 

define the System Password.  If the System Password is not defined, 

the RPC will always start-up in System Mode, allowing unprotected 

access to configuration and switching functions.

•  If the System Password is not defined, the Password Prompt will not 

be displayed when you access the RPC via the Text Interface.  The 

prompt will always be displayed when the RPC is contacted via the 

Web Browser Interface.

•  When the RPC is contacted via Network, the password prompt will 

also include a field for the user name.  If you have not defined a user 

name, then you may leave this field blank, and only the password 

is required to gain access to the unit.  The user name prompt is not 

displayed when the unit is contacted via the Text Interface.

Содержание RPC-4850-8

Страница 1: ...Distributed by i Tech Company LLC TOLL FREE 888 483 2418 EMAIL info i techcompany com WEB www i techcompany com...

Страница 2: ......

Страница 3: ...an effect on overcurrent protection and supply wiring GROUNDING Reliable earthing of this equipment must be maintained Particular attention should be given to supply connections when connecting to pow...

Страница 4: ...ii RPC 4850 8N Remote Power Controller User s Guide...

Страница 5: ...tion Menus 5 5 5 3 1 The General Parameters Menus 5 6 5 3 2 The Serial Parameters Menu 5 9 5 3 3 Circuit Parameters Menus 5 11 5 3 3 1 Circuit Passwords and Co Location Features 5 12 5 3 3 2 The Boot...

Страница 6: ...ters Menu Text Interface 5 7 5 5 Serial Parameters Menu Web Browser Interface 5 9 5 6 Serial Parameters Menu Text Interface 5 9 5 7 Circuit Parameters Menu Web Browser Interface 5 11 5 8 Circuit Param...

Страница 7: ...assure secure access to your equipment The RPC provides two levels of operational passwords the System Administrator Level which allows access to all con guration and switching functions and the User...

Страница 8: ...roughout this manual typefaces and characters have been used to denote the following COURIER FONT Indicates characters typed on the keyboard For example ON 3 or OFF 4 Bold Font Text set in bold face a...

Страница 9: ...Default Parameters To set all parameters to default values rst pull out both the Input Bus A and Bus B circuit breakers to the open position Next press and hold the Default Button then press either I...

Страница 10: ...to two terminal blocks A 15 Amp Circuit Breakers Each circuit includes a 15 Amp breaker B Status Indicators Each circuit includes a Status Indicator which lights when the circuit is switched On C Moun...

Страница 11: ...ting power to the unit make certain to review the Safety Precautions listed at the beginning of this User s Guide The RPC features two separate DC inputs connect power cables to the unit s Circuit A a...

Страница 12: ...LY DC DC CONVERTER INPUT A INPUT B NETWORK INPUT 10BASE T RS232 INPUT 12 LOGIC GROUND RL1 RL2 50A 50A CIRCUIT BREAKER 15A 15A 12 12 RL1 RL2 OUTPUT CKT 1 OUTPUT CKT 2 48 VDC 48 VDC 48 VDC 48 VDC 0 VDC...

Страница 13: ...op Bit No Parity Although the RPC allows these parameters to be easily rede ned for the purpose of this Quick Start procedure it is recommended that you con gure your communications program to accept...

Страница 14: ...et been de ned you can simply click OK without keying in a user name or password The Circuit Status Screen will be displayed as shown in Figure 3 2 Figure 3 2 Circuit Status Screen Web Browser Interfa...

Страница 15: ...mmands a Reboot Circuit If you are communicating with the unit via the Web Browser Interface select the button in the Boot column for Circuit 1 and then click Apply If you are operating the unit via t...

Страница 16: ...you log off using the proper RPC command this ensures that the unit has completely exited from command mode and is not waiting for the inactivity timeout to elapse before allowing additional connecti...

Страница 17: ...install the protective cover supplied with the unit over the power input Make certain that the power cables are securely fastened to the input terminal block and then use the mounting screw receptacl...

Страница 18: ...PC Console RS232 Port Make certain that the Serial Port Mode is set to Console as described in Section 5 3 2 4 3 2 Connecting an External Modem When connecting directly to an external modem use a stan...

Страница 19: ...tem Password is entered the System Mode will be active If a Circuit Password is entered the User Mode will be active The System Password is de ned via the General Parameters menu Section 5 3 1 and the...

Страница 20: ...via network and the Text Interface is available via network modem or local PC The sections that follow describe the procedure for accessing the Web Browser Interface or the Text Interface Note Con gu...

Страница 21: ...The RPC must be connected to your TCP IP Network and your PC must include a communications program such as Hyperterminal or Tera Term Access Via Modem An external modem must be connected to the RPC RS...

Страница 22: ...e ned the unit will display the Password Prompt Key in either the System Password or Circuit Password and press Enter If the System Password has not been de ned the prompt will not be displayed when t...

Страница 23: ...lected parameters will not be activated until you click the Apply button Click Switch Panel to return to the main status screen Text Interface Refer to the Help Screen H then enter the appropriate com...

Страница 24: ...ow you to de ne the following parameters System Password The RPC will display a password prompt when you attempt to access command mode When the System Password is entered at log on the System Mode wi...

Страница 25: ...characters asterisks or quotation marks Site ID De nes a brief text message which can describe the location of the RPC unit Up to 32 characters Default unde ned Notes The Site ID Message cannot begin...

Страница 26: ...ore information please refer to Section 6 4 Default Off Note When this option is enabled security functions are suppressed and users are able to access con guration menus and control circuits without...

Страница 27: ...access the Setup Menus and then click the Serial Parameters button The Serial Parameters Menu will be displayed as shown in Figure 5 5 Text Interface Type C and press Enter The Serial Parameters Menu...

Страница 28: ...ets up the serial Console RS232 Port for use with either a local PC or an external modem Note that when the Port Mode is set to Modem the modem initialization string will be sent every 15 minutes Defa...

Страница 29: ...the number or name of the circuit you wish to con gure The Circuit Parameters Menu will be displayed as shown in Figure 5 8 Note that in this case the major difference between the Web Browser Interfa...

Страница 30: ...uit will react when the Default command D is invoked or after power to the unit has been interrupted and then restored After the default command is invoked or power is restored the RPC will automatica...

Страница 31: ...cess to circuits one through four and that the Boot Sequence Delays for each circuit have been set as follows Circuit 1 1 Second Circuit 2 2 Seconds Circuit 3 5 Seconds Circuit 4 1 Minute If the user...

Страница 32: ...ers Menu Web Browser Interface NETWORK PARAMETERS 1 IP Address 207 212 30 80 2 Subnet Mask 255 255 255 0 3 Gateway Address 207 212 30 1 4 Send MSS 536 5 IP Security MAC Address 00 09 9b 00 90 dd Enter...

Страница 33: ...s depend on the con guration of your individual network Contact your network administrator for appropriate settings The Network Parameters Menus allow the following parameters to be de ned Except wher...

Страница 34: ...s along with the selected permit deny action for each mask a Each Security Mask prompt de nes a speci c IP address or range of addresses Each Mask Action prompt de nes the permit deny action for the c...

Страница 35: ...y by addresses that begin with 192 deny access to 192 1 1 5 Security Mask 1 255 255 255 255 Mask 1 Action Deny Security Mask 2 192 255 255 255 Mask 2 Action Permit Security Mask 3 192 1 1 5 Mask 3 Act...

Страница 36: ...ll be displayed as shown in Figure 5 13 The Telnet Parameters Menus allow the following parameters to be de ned Please note that all parameters listed here are available via both the Web Browser Inter...

Страница 37: ...then click the Web Server Parameters button The Web Server Parameters Menu will be displayed as shown in Figure 5 14 Text Interface Type W and press Enter The Web Server Parameters Menu will be displa...

Страница 38: ...ently de ned con guration As described in Section 7 this provides quick recovery in the event that the unit is accidentally reset to default parameters and also allows you to copy parameters to other...

Страница 39: ...the Web Browser Interface the rst screen that is displayed is the Circuit Status Screen or Switch Panel The Circuit Status Screen Figure 6 1 lists the current On Off status of the RPC s Switched Circu...

Страница 40: ...lick the Boot button in the All Circuits row and then click Apply 6 Set Circuits to Power Up Defaults To set all circuits to their user de ned Power Up Default On Off status click the Default button i...

Страница 41: ...t status of the RPC s Switched DC Circuits and displays the rmware version and currently de ned Site I D Message Normally the Circuit Status Screen will also be redisplayed each time a command is succ...

Страница 42: ...ompleted When switching and reboot operations are initiated Boot Sequence Delay times will be applied as described in Section 5 3 3 2 Remote Power Controller v1 41i Site ID unde ned Display Con gurati...

Страница 43: ...te that the BOOT command can also be entered as BO For example BOOT 1 or BO ATMSWTCH 4 Set Circuits to Power Up Defaults To set each circuit to it s user de ned Power Up Default On Off status type D a...

Страница 44: ...er the number for the circuits that mark the beginning and end of the range separated by a colon For example to switch circuits 1 through 3 On enter the following ON 1 3 Enter 4 All Circuits To apply...

Страница 45: ...is enabled all RPC password security functions are disabled and users are able to access System Level command functions including the con guration menus and control circuits without entering a passwor...

Страница 46: ...using invalid formats or arguments All other status display and con guration commands will still function as normal 6 5 Manual Operation In addition to the command driven functions available via the...

Страница 47: ...erminal etc which allows downloading of ASCII les Note Although this function is only available via the Text Interface parameters that are de ned via the Web Browser Interface will also be sent to the...

Страница 48: ...gure your communications program to upload an ASCII text le 4 Upload the le with the saved parameters If necessary key in the le name and directory path 5 When the upload is complete make certain to...

Страница 49: ...before beginning this upgrade procedure 1 Obtain the update le Firmware modi cations can either be mailed to the customer on a CDR or downloaded from WTI Place the upgrade CDR in your disk drive or c...

Страница 50: ...e 6 Incomplete Upload If the upload is interrupted times out or if the update le becomes corrupted during transfer the RPC will display a screen which asks for con rmation before proceeding To proceed...

Страница 51: ...Apx 1 A Interface Description A 1 Serial Console RS232 Port Interface Figure A 1 Console Port Interface...

Страница 52: ...15 Amps Max per Circuit Total for Circuits One through Eight not to exceed 50 Amps Control Ports Network Port Ethernet 10Base T Console Modem Port DB9M RS232C DTE RS232 Coding Serial ASCII 7 8 Bits N...

Страница 53: ...odel of the unit its serial number and a description of its symptoms If the unit should need to be returned for factory repair it must be accompanied by a Return Authorization number from Customer Ser...

Страница 54: ...d in this publication are trademarks of their respective companies Information and descriptions contained herein are the property of Western Telematic Inc Such information and descriptions may not be...

Страница 55: ...rs 5 18 Web Server 5 19 Con rmation Prompt 5 8 Console Port 2 2 4 2 Apx 1 Baud Rate 5 10 Connection 4 2 Data Bits 5 10 Parity 5 10 Stop Bits 5 10 Contact Information Apx 3 Customer Service Apx 3 D Dat...

Страница 56: ...x 1 S Saving Parameters 5 20 7 1 Sectors 8 1 Security 5 16 Security Level 5 1 Send MSS 5 15 Serial Parameters 5 9 to 5 10 Serial Port Apx 1 Baud Rate 5 10 Data Bits 5 10 Parity 5 10 Stop Bits 5 10 Ser...

Страница 57: ...Notes 1 Notes...

Страница 58: ...Notes 2 RPC 4850 8N Remote Power Controller User s Guide Notes...

Страница 59: ......

Отзывы: