Original Operating Instructions
BATD0050-ES-1-400-1
Troubleshooting
O_BATD0050-ES-1-400-1_V2.6_GB
Page
58
of
72
6.1.6 BAT Error Code 156
Corrective action:
1.
Check
if the Enable switch is pressed (Figure 4).
If the Enable switch is pressed, then
pull out
the Enable switch.
2.
Check
if the cabinet door is closed (Figure 4).
If the cabinet door is opened,
close
the cabinet door.
6.1.7 BAT Error Code 157
Corrective action:
1. It is recommended to replace all surge arresters, if the indication shows a red
flag.
Locate
surge arresters (-F30) and (-F32) (Figure 5).
Use
surge arresters of the spare parts list (Table 9).
2. It is recommended to check all fuses of the notch filter (-F1) and harmonic filter
(-F2.).
Locate
fuses (Figure 5).
Use
fuses of the spare parts list (Table 9).
6.1.8 BAT Error Code 158
Corrective action:
1.
Check
if there is a short-circuit to ground in the battery.
6.1.9 BAT Error Code 159
Corrective action:
1.
Check
that the motor proctecting switch (-F31) is in position I (Figure 5).
6.1.10 BAT Error Codes 161-163
Corrective action:
1.
Contact
customer service.
6.1.11 BAT Error Codes 164
Corrective action:
1.
Contact
customer service.
6.1.12 BAT Error Codes 169
Corrective action:
1.
Contact
customer service.
6.1.13 BAT Error Code 171
Corrective action:
1.
Check
that the motor protecting switch (-F31) is in position
I
2.
Ensure
that the AC voltage has a clockwise rotary field.
Содержание BATD0050-ES-1-400-1
Страница 72: ......