Commissioning
Greenstar Heatslave II External
ErP -
6 720 813 345 (2014/09)
30
Menu 2 parameter
Reset to factory settings
To reset any or all changes made in Menu 2 back to the factory default
setting:
1. Press and hold the
and
buttons for at least five
seconds. The screen will then display code BE and spanner symbol.
Fig. 58
1. Press the
button and “reset” will be displayed with the tick
symbol for three seconds. After three seconds the display will revert
to the normal operation screen.
Fig. 59
Finish pre-commissioning boiler checks
▶ Check the CO
2
levels, refer to table 8 and adjust the air shutter [L].
▶ Check the flue gas temperature is close to the values in table 8.
If the flue gas temperature is too high and the baffles are correctly fitted,
then reduce the oil pump pressure [B] 5-10 p.s.i. to compensate for
nozzle variations.
▶ Turn off the electrical supply.
▶ Isolate the oil supply to the burner.
▶ Remove the oil pressure gauge.
▶ Refit the blanking plug [A].
▶ Check and rectify any oil leaks.
3. Switch on the oil supply.
▶ Switch on the electrical supply.
▶ Restart the boiler and run for 5 minutes.
▶ Recheck the CO
2
levels and if required, adjust the air shutter
setting [D] to obtain the correct CO
2
level.
▶ Refit the sample point cap (hand tighten only, do not over tighten)
and refit the burner cover.
▶ Complete the oil boiler commissioning checklist at the back of this
manual.
Fig. 60
Nominal boiler rating at normal operating temperature using Kerosene (Class C2)
2.7A
Demand /fault
indicator
(blue light) activation
0 = The blue light will only operate as a
flashing fault alert.
1 = The blue light will operate as a boiler
demand light and fault alert.
This is set to 1 by default.
Any changes made to Menu 1 are not reset by these
actions.
APPLIANCE MUST BE SET TO CO
2
LEVELS.
Air settings are approximate, as flue length and nozzle
variations will affect them.
ok
1
reset
6 720 805 209-45.1TL
2
A - B leed & pressure gauge port
B - Pressure adjustment
C - Vacuum gauge port
RIELLO
RDB OIL PUMP
C
B
A
D
6 720 805 209-46.1TL
3
Oil pump pressure
Fuel flow rate
Approximate
flue gas
temperature
Approximate
air setting
Input
(appliance)
Output
(appliance)
Air damper
disk setting
Burner head
Nozzle
bar
psi
Kg/h
l/h
°C
%CO2
kW
kW
Greenstar Heatslave II 12/18 model
0.35 x 80° SR
9.0
132
1.04
1.32
72
11.0
3.0
12.4
12.0
12/15
LD2X Short
0.45 x 60° ES
7.5
110
1.28
1.63
77
11.5
5.0
15.4
15
12/15
LD2X Short
0.55 x 80° ES
7.8
115
1.54
1.96
80
12.0
5.0
18.5
18.0
18
LD2X Short
Greenstar Heatslave II 18/25 model
0.50 x 80° ES
8.5
125
1.58
1.96
76
11.5
3.0
18.5
18.0
18
LD2SX Short
0.60 x 60° ES
8.5
125
1.84
2.33
81
12.0
3.5
22.1
21.5
21.5
LD2SX Short
0.75 x 80° ES
7.5
110
2.15
2.72
87
12.0
4.5
25.7
25.0
25
LD2SX Short
Greenstar Heatslave II 25/32 model
0.75 x 80° ES
7.5
110
2.15
2.72
79
11.5
3.5
25.7
25.0
N/A
T2 Short
0.75 x 80° ES
10.0
147
2.46
3.12
81
12.0
4.5
29.4
28.5
N/A
T2 Short
0.85 x 80° EH
9.5
140
2.78
3.52
86
12.5
5.0
33.0
32.0
N/A
T2 Short
Table 8 Combustion settings