Installation
7
Greenstar 80mm Flexi RF Flue – 6721814542 2019/09
4
Installation
NOTICE:
Flue components
▶ All seals must be greased with the silicone grease provided before
assembly.
▶ Any damaged flue components must be replaced, repairs are not
allowed.
4.1
Creating the chimney opening
NOTICE:
Damage to the appliance
Debris entering the appliance
▶ Do not install the flue duct with the open end facing up the chimney
The horizontal flue pipe connecting appliance and flexible liner must rise
by at least 52mm for every metre of length. This is to ensure the
condensate flows back into the appliance.
▶ The lower edge of the chimney opening is higher than the appliance.
As shown in fig. 6, the height
h
is dependant on the distance
d
. For every
metre the appliance is away from the chimney wall the height must rise
by at least 52mm. The further away the appliance stands from the
chimney wall, the higher the lower edge of the chimney hole must be.
Fig. 6
Positioning the chimney opening
The chimney hole must be large enough to install the flue and allow
access to the joints for servicing.
▶ Make an opening in the chimney wall according to the measurements
▶ Mark the position of elbow support, ensuring that the mark is centred
within the opening made in the chimney wall.
▶ Drill a Ø 10mm hole 60mm deep into the chimney wall.
Fig. 7
Chimney opening
Table 13 Chimney opening
X = the depth of the chimney opening
An additional hole is required to secure the support bar.
▶ Drill a hole into the ledge of the chimney hole as shown opposite,
ensure that the hole is centrally located in the opening.
▶ Insert a suitable wall plug.
Fig. 8
Drilling security hole
0010029146-001
A
B
Minimum mm
150
300
Maximum mm
260
390
A
B
X
Ø 10 mm
55
0010029919-001
A
B
X
Ø 10 mm
55
0010029919-001