KEY TO SYMBOLS

6 720 815 725 (2015/05)

4

manufacturer's instructions by competent persons and that it meets the 
requirements of the appropriate Building Regulations. 

The Benchmark Checklist can be used to demonstrate compliance with 
Building Regulations and should be provided to the customer for future 
reference. 

The guarantee of this product is dependant on the Benchmark checklist 
being completed and the actions undertaken.

Installers are required to carry out installation, commissioning and 
servicing work in accordance with the Benchmark Code of Practice 
which is available from the Heating and Hot water Industry Council who 
manage and promote the scheme. 

Visit 

centralheating.co.uk

 for more information.

HEALTH AND SAFETY

The appliance contains no asbestos and no substances have been used 
in the construction process that contravene the COSHH Regulations 
(Control of Substances Hazardous to Health Regulations 1988).

COMBUSTION AND CORROSIVE MATERIALS

Do not store or use any combustible materials (paper, thinners, paints 
etc.) inside or within the vicinity of the appliance.

Chemically aggressive substances can corrode the appliance and 
invalidate any guarantee.

FITTING AND MODIFICATIONS

Fitting the appliance and any controls to the appliance may only be 
carried out by a competent engineer in accordance with the current Gas 
Safety (Installation and Use) Regulations.

Flue systems must not be modified in any way other than as described in 
the fitting instructions. Any misuse or unauthorised modifications to the 
appliance, flue or associated components and systems could invalidate 
the guarantee. The manufacturer accepts no liability arising from any 
such actions, excluding statutory rights.

SERVICING

Advise the user to have the system serviced annually by a competent, 
qualified Gas Safe registered engineer. Approved spares must be used 
to help maintain the economy, safety and reliability of the appliance.

IMPORTANT

 

The service engineer must complete the Service Record on the 
Benchmark Checklist after each service.

INSTALLATION REGULATIONS

Current Gas Safety (Installation & Use) Regulations:

All gas appliances must be installed by a competent person in 
accordance with the above regulations. 
Failure to install appliances correctly could lead to prosecution.

The appliance must be installed in accordance with, and comply to, the 
current: Gas Safety Regulations, IET Regulations, Building Regulations 
(England), Building Standards (Scotland) (Consolidation), Building 
Regulations (Wales), Building Regulations (Northern Ireland), local 
water by-laws, Health & Safety Document 635 (The Electricity at Work 
Regulations 1989) and any other local requirements.

EU Regulations No. 811/2013 - Energy Labelling.

BUILDING REGULATIONS PART L 1A 2013

If the installation is in a new build property or is a first time installation in 
an existing property, heating systems must conform to current building 
regulations Part L1a.
All new heating systems in dwellings must have at least two heating 
zones. Each of these zones will be operated separately by both time and 
temperature controls.
The exception to this are single storey, open plan dwellings where the 
living area is more than 70% of the total useable floor area. Then this 
type of dwelling can be controlled as one zone.

All radiators must have TRVs fitted, where reasonable, in all rooms 
except bathrooms and rooms with thermostats.

BUILDING REGULATIONS PART L 1B 2013 - BOILER REPLACEMENT

For boiler replacement on an existing system, it is not necessary to zone 
the system, compliance with the zone requirements can be achieved by 
a single room thermostat or programmable room thermostat.

BRITISH STANDARDS

Where no specific instruction is given, reference should be made to the 
relevant British Standard codes of Practice.

BS7074:1 Code of practice for domestic and hot water supply
BS6891 Installation of low pressure gas pipe work up to 35mm (R1¼ )
BS5546 Installation of gas hot water supplies for domestic purposes
EN12828 Central heating for domestic premises
BS5440:1 Flues and ventilation for gas appliances of rated heating not 
exceeding 70kW (net): Flues
BS5440:2 Flues and ventilation for gas appliances of rated heating not 
exceeding 70kW (net): Air Supply
BS7593 Treatment of water in domestic hot water central heating 
systems
BS6798 Installation of gas fired boilers of rated input up to 70kW (net)

Irish Standards

The relevant Irish standards should be followed, including:

• ECTI National rules for electrical installations
• IS 813:2002 for Domestic Gas Installations.

LPG Installations

An appliance using L.P.G. must not be installed in a room or internal 
space below ground level unless one side of the building is open to the 
ground. 

Timber framed building

:

Where the boiler is to be fitted to a timber framed building the guidelines 
laid down in BS5440: Part 1 and IGE "Gas Installations in Timber Frame 
Buildings” should be adhered to.

Potable water:

All seals, joints and compounds (including flux and solder) and 
components used as part of the secondary domestic water system must 
be approved by WRAS.

CH Water:

Artificially softened water must not be used to fill the central heating 
system.

BOILER FEATURES

• Pre-wired and pre-plumbed
• Galvanised steel inner frame
• Digital control system
• FX/Greenstar Sense controls
• Automatic ignition
• Direct burner ignition electrodes
• Built-in frost protection
• Built-in fault finding diagnostics
• Automatic gas valve
• Modulating combustion air fan with speed regulator
• CH temperature sensor & control
• Pump anti-seizure protection
• Flue gas temperature sensor
• Condensate siphonic trap
• DHW flow sensor & temperature control
• Plate type DHW heat exchanger
• Low Energy Modulating pump

Содержание GREENSTAR 29CDi Classic ErP

Страница 1: ...ATER 6 720 815 725 2015 05 The appliances are for use with Natural Gas or L P G Cat II 2H3P type C13 C33 C53 Natural Gas 29CDi Classic ErP GC number 47 406 65 34CDi Classic ErP GC number 47 406 67 38C...

Страница 2: ...t 26 4 5 2 60 mm Plume management kit 26 4 5 3 Adjusting the standard terminal length 26 4 5 4 Installing the standard flue 27 4 5 5 Flue terminal plume re direction 27 4 6 Condensate connection 28 4...

Страница 3: ...eywords at the start of a warning indicate the type and seriousness of the ensuing risk if measures to prevent the risk are not taken This symbol indicates important information where there is no risk...

Страница 4: ...013 If the installation is in a new build property or is a first time installation in an existing property heating systems must conform to current building regulations Part L1a All new heating systems...

Страница 5: ...hung gas fired condensing combi boiler for central heating and domestic hot water B Wall mounting plate with hanging bracket C Pre plumbing manifold D Hardware pack E ErP energy label F Literature pac...

Страница 6: ...APPLIANCE INFORMATION 6 720 815 725 2015 05 6 2 2 LAYOUT COMPONENTS Fig 3 Boiler components 2 3 4 5 6 8 15 9 10 13 12 14 16 17 20 23 24 25 26 27 28 1 22 21 18 19 7 6 720 815 725 06 1O 11...

Страница 7: ...AN PRESSURE TEST POINT 26 FAN 27 PRIMARY SENSOR 28 EXPANSION VESSEL Table 3 Main boiler components 6 34 41 33 29 30 32 31 6 720 812 176 07 1O 7 40 8 41 36 35 37 38 39 9 29 FLOW TURBINE 30 UNUSED PORT...

Страница 8: ...0 5 10 5 8 6 12 3 15 5 15 5 Min rated heat output net 80 60 C kW 7 7 7 7 9 4 9 4 7 7 11 0 13 9 13 9 Min rated heat input net kW 8 0 8 0 9 8 9 8 8 0 11 5 14 5 14 5 Max flow temperature nominal C 90 90...

Страница 9: ...asonal space heating energy efficiency s 92 92 92 92 Energy efficiency class A A A A Useful heat output At rated heat output and high temperature regime 1 1 High temperature regime means 60 C return t...

Страница 10: ...30 0 30 0 30 0 At 30 of rated heat output and low temperature regime 2 2 Low temperature means for condensing boilers 30 C for low temperature boilers 37 C and for other heaters 50 C return temperatur...

Страница 11: ...the boiler must be in accordance with BS6891 Under no circumstance should the size of the gas supply pipe be less than 22 mm The meter or regulator and pipe work to the meter must be checked preferabl...

Страница 12: ...t hot and cold mains water can be used with the approval of the local water authority and must be the over rim flushingtypewithshroudedoutletstopreventthefittingofhandheld sprays SEALED PRIMARY SYSTEM...

Страница 13: ...ould be removed using a proprietary condensate pump of a specification recommended by the boiler or condensate pump manufacturer The pump outlet pipe should discharge to a suitable internal foul water...

Страница 14: ...from wind chill Pipe drainage will be improved if the end is cut at 45 as opposed to a straight cut Fig 14 External disposal CONDENSATE SOAK AWAY Thecondensatedrainagepipemayberunaboveorbelowthegroun...

Страница 15: ...a soakaway or a condensate pump Use an esxternal drain point on the system to prevent excess system water being drawn through the saokaway or condensate pump NOTICE Unheated internal areas Internal pi...

Страница 16: ...tition The partition may be perforated if required by holes not exceeding 13 mm in diameter If the appliance is fitted into a cupboard or a compartment is built around the appliance after installation...

Страница 17: ...d installed pipe work can be installed to the valves on the manifold The pipes can be run below the boiler or alternatively up behind the boiler RUNNING PIPES BEHIND THE BOILER If the boiler pipes are...

Страница 18: ...2 0 metres of straight flue Each 45 bend used is equivalent to 1 0 metre of straight flue Telescopic horizontal flue Flue option 1 100mm 125mm 29CDi ErP 570mm 600mm 34CDi ErP 570mm 600mm 38CDi ErP 570...

Страница 19: ...PRE INSTALLATION 6 720 815 725 2015 05 19 Fig 22 350 mm 570 mm 130 mm Min Flat roof 300 mm 500 mm Pitched roof 2 3 4 5 6 10 9 8 7 1 6720643895 12 1Wo...

Страница 20: ...e and drains 16 The dimension below eaves balconies and car ports can be reduced to 25mm as long as the flue terminal is extended to clear any overhang External flue joints must be sealed with suitabl...

Страница 21: ...mthelowestpointofthebalcony or overhang 9 1 200mm from an opening in a car port on the same wall e g door or window leading into the dwelling 10 600mm distance to a surface facing a terminal unless it...

Страница 22: ...ked before ascending ladder to loft space Two sets of steps should be used Two people should share the lifting of the boiler up to the loft hatch where the boiler is entered into the loft space tilted...

Страница 23: ...ackaging base B and place safely away from the working area REMOVING OUTER CASE 8 Loosen but do not remove the 2 screws E securing boiler casing at the bottom of the appliance 9 Pull upwards to releas...

Страница 24: ...r rear outlet 3 or for side outlet 4 For the 60 100 mm flue make a 125 mm diameter hole through the wall using a core drill or similar For flues using an optional weather collar fitted from inside the...

Страница 25: ...the system pipes Connect the gas supply to the boiler gas cock 22mm compression Connect cold water in and DHW out to the boiler s 15mm compression connectors Connect the CH flow and CH return pipes to...

Страница 26: ...ith plume management extension components Fig 34 60mm PLUME MANAGEMENT KIT 7 716 191 086 replaces the plume deflector in the 60 100mm telescopic flue terminal 4 5 3 ADJUSTING THE STANDARD TERMINAL LEN...

Страница 27: ...e terminal 2 as shown Fig 38 Flue installation 4 5 5 FLUE TERMINAL PLUME RE DIRECTION The flue discharge can be re directed allowing some plume redirection control alternatively a complete plume manag...

Страница 28: ...onnection Aligntheinstallationsideplasticpipeworkthroughthepre plumbing manifold Connect the installation side plastic pipework to the end of the condensate hose Push the plastic pipework inside the c...

Страница 29: ...or 7 Optional external frost thermostat connection ST6 Connect frost thermostat supply LIVE to terminal FS Connect frost thermostat SWITCHED LIVE to terminal FR 8 230V room thermostat and or external...

Страница 30: ...y 230V EXTERNAL CONTROLS OPTION WORCESTER 24V CONTROLS OPTION PLUG IN POINT under blanking cover on fascia EMS BUS contacts for FX Sense controls Outside sensor FW 100 Live Supply Live Return Neutral...

Страница 31: ...ck that the condensate pipe has been connected to the adaptor Fig 47 5 2 FILLING THE SYSTEM Ensure all system and boiler drain points are closed Remove the bottom panel if fitted Open the isolating va...

Страница 32: ...DHW temperature control I Central heating temperature control J Performance test button K Service button L Burner indicator GREEN M On off and fault indicator BLUE N Automatic air vent Fig 50 Control...

Страница 33: ...when the inhibitor was added to the system on the guarantee card 5 5 COMMISSIONING Fig 52 Control panel NOTICE ARTIFICIALLY SOFTENED WATER MUST NOT BE USED TO FILL THE CENTRAL HEATING SYSTEM The pH va...

Страница 34: ...er to the figure below for natural gas pressures The pressure at the boiler must not be less than the pressure read at the meter minus 1 mbar Thepressuredropfromthemetertothegasvalvemustnotbemorethan...

Страница 35: ...15 minutes Close the gas isolation valve Remove the manometer Re seal the screw in the gas inlet pressure test point Open the gas isolation valve Ensure that there are no gas leaks Replace the outer c...

Страница 36: ...nalysermusthavebeencalibratedas specified by the manufacturer The installer must be competent in the use of the analyser Check and zero the analyser in fresh air as specified by the manufacturer The a...

Страница 37: ...the panel up against the underside of the boiler and slide towards the rear until it is fully engaged HANDOVER Complete the Benchmark check list The fascia cover is opened by pulling the flap D towar...

Страница 38: ...performance of the boiler can be checked via the flue turret sample points Fig 59 Flue turret test points With the boiler case on and the boiler running at maximum output refer to paragraph SET THE B...

Страница 39: ...ol panel A ON OFF button B Cover or optional plug in controller C Display D System pressure gauge E Reset button F ECO button G Holiday button H DHW temperature control I Central heating control J Per...

Страница 40: ...R Remove outer case and base panel and isolate the appliance from power 1 Remove cleaning access cover B seal C and metal plate D securing it if present Fig 66 Cleaning heat exchanger 2 Loosen any dep...

Страница 41: ...e fan Slacken fully the rear securing bolt F Remove the burner cover plate G Fig 68 3 Remove the burner H and clean components Do not use a wire brush Fig 69 6 1 6 TO CHECK THE DIAPHRAGM IN BURNER COV...

Страница 42: ...seal inlet pressure point on gas valve Fit new plastic sealing cover onto the max adjuster Replace the brass screw over the min adjuster on the valve Re assemble and refit boiler case Fig 71 Setting...

Страница 43: ...from connector coat new sensor with heat conductive paste and replace 4 OVERHEAT THERMOSTAT Remove two electrical connectors from thermostat Unscrew the sensor 5 FLUE LIMIT THERMOSTAT Remove electric...

Страница 44: ...tion C to gas valve Undo two securing screws D on the underside of casing Pull valve up and forward out of boiler Disconnect electrical connections Replace valve with new seals and check for gas tight...

Страница 45: ...or from fan Remove condensate trap see page 41 1 Undo the union connection A from the top of the gas valve Remove wire clip B from air gas adjustment assembly C then pull gas pipe down 2 Unscrew two s...

Страница 46: ...Check that the boiler is completely isolated from the gas supply Fig 81 Top panel 2 Remove clips C and unscrew the two bolts D Unscrew and remove the two hexagon screws E securing the fan Slacken ful...

Страница 47: ...D Fig 88 Heat exchanger removal 3 4 Undo flue connection E from sump F Pull flue pipe up Remove the heat exchanger Fig 89 Heat exchanger removal 4 17 DIVERTER VALVE MOTOR There is no need to drain the...

Страница 48: ...ut of the housing and remove To refit follow the above in reverse Fig 92 Auto Air Vent removal 20 DHW TEMPERATURE SENSOR Ensure the domestic hot water circuit is fully drained Disconnect the electrica...

Страница 49: ...withdraw the flow restrictor housing If the regulator housing has become stuck a pair of long nosed pliers may be used to grip the housing To refit follow the above in reverse Ensure any seals that h...

Страница 50: ...ssure relief valve Disconnect the drain pipe from the drain tap see e g step 1 in Fig 96 Release the locking devices that secure the two copper water pipes leading to the combustion chamber by squeezi...

Страница 51: ...PLASTIC PROTECTION DEVICE Ensure the system is fully drained Disconnect all pipes connected to the pump housing Remove the electrical connection to the pump Withdraw the metal clip to the right of the...

Страница 52: ...valve 8 718 221 347 0 GC No H56 469 Temperature limit sensor 8 722 963 858 0 GC No H08 291 Electrodes 8 716 771 932 0 GC No H22 458 Flow reg Type E 11 litre brown8 716 107 044 0 Flow reg Type E 12 li...

Страница 53: ...trol sensor primary8 714 500 087 0 GC No E74 536 Heat Exchanger inspection cover seal 8 710 103 153 0 Pressure relief valve 8 716 106 431 0 GC No H09 750 Auto Air Vent 8 716 106 445 0 Flue overheat th...

Страница 54: ...d the breaking and remaking of electrical connections check a EARTH CONTINUITY b SHORT CIRCUIT CHECK c POLARITY d RESISTANCE TO EARTH You can also use this menu item to check the hot water flow rate a...

Страница 55: ...setpoint by 10K Diverter Value in CH position pump ON Gas value OFF Fan overrun 30 seconds Over temperature shut down if water temperature exceeds set value CH setpoint 90 seconds stabilisation period...

Страница 56: ...DHW position Pump ON 5th attempt Spark ignition 4 seconds Stop spark Wait 10 seconds BURNER LIT IGNITION SEQUENCE see details GREEN FLAME LIGHT ON DEMAND END DEMAND END Fan gas modulation to achieve s...

Страница 57: ...7 5 PROTECTION FUNCTION Holiday mode set to ON All other demands not active Frost protection active DHW demand active Pump runs for 5 seconds every 24 hours Pump antiseize Run autofroststat function...

Страница 58: ...SKRQH 1R DV VDIH UHJLVWHU 1R 5HFRUG W PD UDWH 2 SSP AND 2 W PLQ UDWH KHUH 3RVVLEOH 2 SSP AND 2 RPPHQWV 6LJQDWXUH SERVICE 04 DWH QJLQHHU QDPH RPSDQ QDPH 7HOHSKRQH 1R DV VDIH UHJLVWHU 1R 5HFRUG W PD UDW...

Страница 59: ...HU LQWHUORFN 3URYLGHG ALL SYSTEMS 7KH V VWHP KDV EHHQ XVKHG DQG FOHDQHG LQ DFFRUGDQFH ZLWK 6 DQG ERLOHU PDQXIDFWXUHU V LQVWUXFWLRQV Yes KDW V VWHP FOHDQHU ZDV XVHG KDW LQKLELWRU ZDV XVHG 4XDQWLW OLWUH...

Страница 60: ...9669 Worcester Bosch Group Cotswold Way Warndon Worcester WR4 9SW Tel 0330 123 9559 Worcester Bosch Group is a brand name of Bosch Thermotechnology Ltd worcester bosch co uk 6 720 815 725 2015 05 WORC...

Отзывы: