TROUBLESHOOTING - FR110
8 716 115 748 (2009/09)
66
Fault 59
Mass flow rate in solar system too high/
low.
201
Mass flow rate in solar system for
collector group 1 is too high.
Set mass flow in solar system
correctly (e.g. increase/
decrease pump speed) and if
necessary open or close flow
restrictor more on solar station.
Guide figure: 20 - 40 kg/m
2
of
collector area per hour.
Check setting for collector area,
type and climate zone on Solar
optimisation menu.
202
Mass flow rate in solar system for
collector group 1 is too low.
Information displayed
(
Æ
items 1, 3 and 4 in Fig.
17
)
Text
Code Cause
Remedy
Tab. 32