Supplied By www.heating spares.co Tel. 0161 620 6677
RECTIFYING FAULTS
8 716 115 748 (2009/09)
28
7.3
NOTES ON USING THE FAULT CODE TABLES
The procedure is best described with the aid of an
example:
•
Work through the table from top to bottom and from
left to right.
•
First make a note of the present settings and restore
them before leaving the appliance.
•
Read question
1.
(Check column) and depending on
the answer (yes or no) read the action required from
the relevant box and carry out the instruction given;
ignore the other answer.
For example:
if the burner
flame is visible, follow the instructions for
yes
, i.e. go
to 5.!
•
“go to 5” means go to number 5., ignoring the steps
in between.
In this example:
check the flue is clear by testing the
CO
2
level.
•
If the appliance is locked (
reset
button and the fault
indicator LED are flashing), press the
reset
button.
•
If the fault has been rectified, the appliance will then
start up without indicating a fault and the fault
isolation procedure is complete.
•
If the fault is still present after performing the reset
action and, if necessary, restarting the appliance,
move on to the next step in the fault isolation
procedure.
•
If another fault code is displayed, work through the
fault code table for that code
Fig. 15 Example of fault code table
EA
and
flashing.
Flame not detected
Check
Action
1.
Is a burner flame visible?
yes:
↓
5.
no:
↓
2.
2.
Is the gas cock turned on?
yes:
Ø 5.
no:
B
Open the gas cock.
B
Press button
.
EA?
↓
3.
3.
Has the thermal cut-out on the gas
cock tripped?
yes:
...
no:
↓
...
4. ...
...
5. ...
Problem with flue?
B
Check CO
2
level in combustion
air.
Is CO
2
level above 0,2 % ?
yes:
Check flue.
no:
↓
...
6 720 612 126-01.1O