Manual 37259C
SPM-D11 - Synchronizing Unit
© Woodward
Page 71/79
Option
Parameter
100/400V; 1/5 A
Adjustment range
Standard
setting
Customer settings
CONFIGURE SYNCHRONIZATION
Synchronizing functions
ON/OFF ON
on
off
on
off
Synchronization df
max
0.02 to 0.49 Hz
0.18 Hz
Synchronization df
min
0.00 to
-0.49 Hz
-0.10 Hz
Synchronization dV
max
[1] 1 to 20 V, [4] 1 to 60 V
24 V
Synchronization Brk.hold T>
0.04 to 0.50 s
0.20 s
Phase matching
ON/OFF OFF
on
off
on
off
Phase matching Max phase <
0 to 60°
7 °
Slip synchroniz. TClose GCB
40 to 300 ms
80 ms
Slip synchroniz.Max phase <
0 to 60 °
7 °
Phase matching
Dwell time
0.2 to 10.0 s
10.0 s
Phase matching
Gain
1 to 36
2
Phase matching
df start
0.02 to 0.25 Hz
0.20 Hz
CONFIGURE SYNCHRONIZATION TIME
Sync.time contr.
ON/OFF OFF
on
off
on
off
Sync.time contr. Delay time
10 to 999 s
120 s
CONFIGURE DEAD BUS
Gen. circ.break.Gen.schalter
ON/OFF OFF
on
off
on
off
Dead bus op. GCB
df max
0.05 to 5.00 Hz
0.25 Hz
Dead bus op. GCB
dV max
[1] 1 to 20 V, [4] 1 to 60 V
40 V
CONFIGURE WATCHDOGS
Reverse/min.pow. Monitoring
ON/OFF OFF
on
off
on
off
Reverse/min.pow. Threshold
-99 to
99 %
-20 %
Reverse/min.pow. Delay
0.1 to 99.9 s
1.0 s
Gen. overload
Monitoring
ON/OFF OFF
on
off
on
off
Gen. overload
Threshold.
0 to 150 %
120 %
Gen. overload
Delay time
0 to 99 s
20 s
Gen.frequency- Monitoring
ON/OFF OFF
on
off
on
off
Gen. overfreq.
f >
40.0 to 70.0 Hz
55.0 Hz
Gen. overfreq.
Delay time
0.04 to 9.98 s
3.00 s
Gen. underfreq.
f <
40.0 to 70.0 Hz
45.0 Hz
Gen. underfreq. Delay time
0.04 to 9.98 s
3.00 s
Gen.voltage- Monitoring
ON/OFF OFF
on
off
on
off
Gen.overvoltage U
>
[1] 20 to 150 V; [4] 20 to 520 V
460 V
Gen.overvoltage Delay time
0.04 to 9.98 s
3.00 s
Gen.undervoltage U
<
[1] 20 to 150 V; [4] 20 to -520 V
340V
Gen.undervoltage Delay time
0.04 to 9.98 s
3.00 s
Auto-acknowledge Messages
ON/OFF ON
on
off
on
off
Acknowledge Message
aft
1 to 99 s
1 s
CONFIGURE PASSWORDS
Define level 1
code
0000 to 9999
0001
Define level 2
code
0000 to 9999
0002